Carrier AQUASNAP 30RA010-055 Product Data page 31

Air-cooled chillers 10 to 55 nominal tons (25 to 200 kw)
Hide thumbs Also See for AQUASNAP 30RA010-055:
Table of Contents

Advertisement

FAN ELECTRICAL DATA
UNIT VOLTAGE
UNIT
Circuit A
30RA
V-Hz (3 Ph)
Quantity
230-60
208/230-60
010
460-60
575-60
380-60
230-60
208/230-60
015
460-60
575-60
380-60
230-60
208/230-60
018
460-60
575-60
380-60
230-60
208/230-60
022
460-60
575-60
380-60
230-60
208/230-60
025
460-60
575-60
380-60
230-60
208/230-60
030
460-60
575-60
380-60
230-60
208/230-60
035
460-60
575-60
380-60
230-60
208/230-60
040
460-60
575-60
380-60
230-60
208/230-60
045
460-60
575-60
380-60
230-60
208/230-60
050
460-60
575-60
380-60
230-60
208/230-60
055
460-60
575-60
380-60
LEGEND
FLA — Full Load Amps
STANDARD CONDENSER FANS
FLA
Circuit B
(each)
Quantity
(each)
1
7.6
1
8.4
1
3.8
1
3.0
1
4.6
1
7.6
1
8.4
1
3.8
1
3.0
1
4.6
1
7.6
1
8.4
1
3.8
1
3.0
1
4.6
2
4.8
2
5.3
2
2.4
2
1.9
2
2.9
2
4.8
2
5.3
2
2.4
2
1.9
2
2.9
2
4.8
2
5.3
2
2.4
2
1.9
2
2.9
2
4.8
1
2
5.3
1
2
2.4
1
2
1.9
1
2
2.9
1
2
4.8
1
2
5.3
1
2
2.4
1
2
1.9
1
2
2.9
1
2
4.8
2
2
5.3
2
2
2.4
2
2
1.9
2
2
2.9
2
2
4.8
2
2
5.3
2
2
2.4
2
2
1.9
2
2
2.9
2
2
4.8
2
2
5.3
2
2
2.4
2
2
1.9
2
2
2.9
2
PUMP
PUMP
OPTION
SIZE
FLA
'A' or 'F'
1.5 HP
'B', 'C'
2.0 HP
'G' or 'H'
'D' or 'J'
3.0 HP
'E' or 'K'
5.0 HP
LEGEND
FLA — Full Load Amps
LRA — Locked Rotor Amps
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed minimum and max-
imum limits. Maximum allowable phase imbalance is: voltage, 2%;
amps 10%.
2. All units/modules have single point primary power connection. (Each
unit/module requires its own power supply.) Main power must be sup-
plied from a field-supplied disconnect.
7.6
3. The unit control circuit power transformer (24 v, single-phase for all
8.4
voltages) is factory supplied.
3.8
4. Cooler heaters are wired into the main power circuit so they are always
3.0
operable as long as the disconnect is on, even if any safety device is
4.6
open, and the unit ON/OFF switch is in the OFF position.
7.6
5. Incoming wire size ranges are shown below:
8.4
a. Size 010-030 terminal block no. 8 - no. 2/0 AWG (American
3.8
Wire Gage)
3.0
b. Size 035-055 terminal block no. 6 - 350 kcmil
4.6
c. 60 and 100 amp non-fused disconnect option no. 6 - no. 1 AWG
4.8
d. 250 amp non-fused disconnect option no. 6 AWG - 350 kcmil
5.3
2.4
1.9
ACCESSORY TANK — ELECTRICAL DATA
2.9
4.8
5.3
30RA-
2.4
1.9
900---
(1-Ph)
2.9
4.8
001
230-60
5.3
2.4
009
230-60
1.9
2.9
010
230-60
LEGEND
FLA
— Full Load Amps
PUMP ELECTRICAL DATA
UNIT VOLTAGE
PUMP
RPM
V-Hz (3 Ph)
3500
230-60
3500
208/230-60
3500
460-60
3500
575-60
3500
380-60
3490
230-60
3490
208/230-60
3490
460-60
3490
575-60
3490
380-60
3480
230-60
3480
208/230-60
3480
460-60
3480
575-60
3480
380-60
3450
230-60
3450
208/230-60
3450
460-60
3450
575-60
3450
380-60
UNIT VOLTAGE
Supplied
V-Hz
QUANTITY
REQUIRED
Min
Max
207
253
207
253
207
253
FLA
LRA
(each)
(each)
4.0
32.0
4.4
36.0
2.0
16.0
1.6
14.4
2.4
21.8
5.2
42.0
5.8
47.0
2.6
21.0
2.1
18.8
3.1
28.4
7.4
53.0
8.2
58.0
3.7
26.5
3.0
25.6
4.5
38.7
12.6
126.0
13.9
136.8
6.3
63.0
5.0
55.4
7.6
83.9
POWER
SUPPLY
FLA
1
14.1
1
14.1
1
28.2
31