Maximum Heating Setpoint; Uv Light Reminder; Humidifier Pad Reminder - Carrier Performance TP-PRH-A Installation Instructions Manual

Performance series edge thermidistat control
Hide thumbs Also See for Performance TP-PRH-A:
Table of Contents

Advertisement

Default is 52_F/11_C (based on the adjustable deadband default = 2).
Option 27 — Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint. The
range is based on the adjustable deadband value Option 11, such that the minimum
of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband.
Default is 88_F/31_C (based on the adjustable deadband default = 2).
Option 28 — UV Light Reminder
This selection allows the installer to select the number of months after which the
UV Light icon will be displayed to indicate to the homeowner that it is time to call
the dealer to have the UV Lights replaced. Selections available are OF (off), 6, 12,
18, 24, 30, 36, 42, 48.
OF (off) — The UV Light reminder is turned off and will never be displayed.
6- - 48 — The number of months after which the UV Light reminder will be
displayed, "CHECK UV LIGHT".
Default is OF (off).
Option 29 — Humidifier Pad Reminder
This selects the number of months after which the Humidifier Pad Reminder icon
will be displayed. This is not based on run time.
OF (off) — The Humidifier Pad Reminder is disabled and will never be displayed.
1- - 24 — The number of months after which the Humidifier Pad Reminder icon will
be displayed, "CHECK HUM PAD".
Default is OF (off).