Insulation Of Refrigerant Tubing; Taping The Tubes; Finishing The Installation - Sanyo SAP-CMRV1424EH Technical & Service Manual

Dc inverter multi-system air conditioner
Table of Contents

Advertisement

Be sure to match refrigerant
CAUTION
tubing and electric wiring
between indoor and outdoor
units. For more details, refer to
"Tubing Check Control" in the
Technical & Service Manual.

3-7. Insulation of Refrigerant Tubing

IMPORTANT
To prevent heat loss and wet floors due to dripping of con-
densation, both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum
8 mm. (Fig. 17)

3-8. Taping the Tubes

After a tube has been insulated,
CAUTION
never try to bend it into a
narrow curve, as this may
cause the tube to break or
crack.
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with
armoring tape. The drain hose may also be included
and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As
you wrap the tubing, overlap half of each previous tape
turn. (Fig. 18)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 120 cm.
NOTE
Do not wind the armoring tape too tightly, since this will
decrease the heat insulation effect. Also, be sure the con-
densation drain hose splits away from the bundle and drips
clear of the unit and the tubing.

3-9. Finishing the Installation

After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 19)
Torque wrench
Indoor unit
Min.
8 mm
Apply putty here
15
Spanner
Outdoor unit
Fig. 15
Insulation
Fig. 16
Insulation
Thickness:
min. 8 mm
Fig. 17
Clamp
Insulated tubes
Fig. 18
Tubing
Fig. 19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents