Insulation Of Refrigerant Tubing - Sanyo CM1972A Technical & Service Manual

Dc inverter multi-system air conditioner
Hide thumbs Also See for CM1972A:
Table of Contents

Advertisement

Outdoor Unit CM2472A
Indoor unit
Wide tube
O.D.1/2"
O.D.3/8"
O.D.3/8"
O.D.3/8"
Narrow tube
O.D.1/4"
O.D.1/4"
O.D.1/4"
O.D.1/4"

Insulation of Refrigerant Tubing

IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min.5/16"(8 mm).
After a tube has been insulated,
never try to bend it into a narrow
CAUTION
curve because it can cause the tube
to break or crack.
Outdoor unit
Service valve on
wide tube
DW
CW
BW
AW
Header
Electric
expansion
Service valve on
valve
narrow tube
M
DN
M
CN
M
BN
M
AN
Strainer
22
Sub
Main
accumulator
accumulator
High pressure
switch
H.P.
Header
Thickness:
Min.5/16"(8 mm)
Wide tube
Cooling cycle
Insulation
Thickness:
Min.5/16"(8 mm)
Narrow tube