Precautions Before Performing Inspection Or Repair - Sanyo SAP-CMRV1424EH Technical & Service Manual

Dc inverter multi-system air conditioner
Table of Contents

Advertisement

8. TROUBLESHOOTING

8-1. Precautions before Performing Inspection or Repair

Both the indoor unit and outdoor unit include electronic control circuits.
Be sure to pay attention to the following before inspecting or repairing the outdoor-
side electronic circuits.
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an
electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required
for the charge to dissipate.
Be careful not to touch any electrified parts before the control circuit board Power Lamp (red) turns OFF.
If the outdoor control circuit board is normal, approximately 180 seconds will be required for the charge to
dissipate. However, allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble
with the outdoor control circuit board.
For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required to
discharge the high-capacity electrolytic capacitors.
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents