Detailed cooling capacities* continued
EVAPORATOR
AIR
75
Capacity
MBtuh†
System
CFM
EWB
Total
Sens‡
72
69.2
34.7
67
64.9
45.1
1750
63††
61.1
44.2
62
60.3
55.1
57
58.7
58.7
72
69.9
36.1
67
65.6
47.8
2000
63††
61.8
46.7
62
61.3
58.8
57
60.6
60.6
72
70.3
37.4
67
66.0
50.3
2250
63††
62.3
49.0
62
62.2
61.8
57
62.1
62.1
Indoor
Section
Size
CC5A/CD5AW
060
CK5A/CK5BX
060
FB4(A,B)NB
070
FC4(B,C)NB
070
FV4(A,B)NB
006
FX4(A,B)NB
060
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kw is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
22
CONDENSER ENTERING AIR TEMPERATURES °F
85
Capacity
Total
Total
MBtuh†
System
Total
Sens‡
Total
kW**
kW**
38YZA060-31, 32 Outdoor Section With FX4(A,B)NB060 Indoor Section
4.68
66.0
33.5
5.17
4.63
61.9
43.9
5.13
4.60
58.0
42.8
5.08
4.59
57.3
53.6
5.07
4.57
56.2
56.2
5.06
4.79
66.5
34.9
5.29
4.75
62.5
46.6
5.24
4.71
59.0
45.4
5.20
4.70
58.2
57.1
5.19
4.70
57.9
57.9
5.18
4.90
67.3
36.4
5.41
4.86
62.9
49.1
5.35
4.82
59.8
47.9
5.33
4.82
59.2
59.2
5.30
4.82
59.3
59.3
5.31
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Capacity
Power
0.97
0.98
0.99
0.99
1.00
0.99
95
105
Capacity
Capacity
Total
MBtuh†
MBtuh†
System
Sens‡
Total
Sens‡
kW**
63.2
32.5
5.74
60.2
31.4
58.8
42.6
5.68
55.7
41.4
55.5
41.7
5.65
52.5
40.4
54.6
52.3
5.62
51.7
50.8
54.0
54.0
5.61
51.5
51.5
63.6
33.9
5.85
60.5
32.8
59.4
45.3
5.79
56.0
44.0
56.0
44.1
5.75
52.9
42.8
55.9
55.7
5.76
53.2
53.2
55.5
55.5
5.74
52.9
52.9
63.8
35.1
5.96
60.6
34.1
59.7
47.8
5.90
56.2
46.4
56.3
46.4
5.86
53.1
45.1
57.0
57.0
5.87
54.3
54.3
56.7
56.7
5.86
54.0
54.0
Indoor
Section
40FKA/FK4CNB
1.02
COILS + 58CV(A,X)110-22 VARIABLE SPEED FURNACE
1.02
CD5PX
1.04
COILS + 58CV(A,X)155-22 VARIABLE SPEED FURNACE
1.04
CC5A/CD5AW
1.00
1.04
115
Capacity
Total
Total
MBtuh†
System
System
Total
Sens‡
kW**
kW**
6.37
56.5
30.1
7.04
6.29
52.2
40.0
6.95
6.26
49.3
39.0
6.93
6.23
48.8
48.8
6.90
6.23
48.9
48.9
6.91
6.48
56.6
31.4
7.14
6.40
52.4
42.6
7.06
6.36
49.5
41.4
7.03
6.37
50.4
50.4
7.06
6.35
50.1
50.1
7.03
6.58
56.6
32.6
7.24
6.50
53.2
45.2
7.19
6.47
49.7
43.5
7.13
6.49
51.3
51.3
7.17
6.47
51.0
51.0
7.15
Cooling
Size
Capacity
006
1.01
060
0.97
060
0.97
125
Capacity
Total
MBtuh†
System
Total
Sens‡
kW**
52.3
28.6
7.77
48.4
38.5
7.68
45.6
37.4
7.66
45.8
45.8
7.64
45.9
45.9
7.65
52.3
29.9
7.87
49.1
41.3
7.82
45.8
39.7
7.76
47.3
47.3
7.80
46.9
46.9
7.77
52.2
31.1
7.96
49.7
43.8
7.96
45.8
41.9
7.86
48.5
48.5
7.95
48.2
48.2
7.92
Power
1.00
1.00
0.98