GAS CONNECTION

• PIPE JOINT COMPOUNDS RESISTANT TO PROPANE
GASES MUST BE USED.
• BEFORE OPERATING THIS HOT PLATE, CHECK
PIPE JOINTS FOR LEAKS BY USING A SOAP AND WA-
TER SOLUTION ONLY. DO NOT USE AN OPEN FLAME!
Figure 1
Main Gas
Connection
FOR YOUR SAFETY: Do not store or use gasoline or
other fl ammable vapors and liquids in the vicinity of
this or any other appliance.
Connect the hot plate to the main gas supply line at
the rear of the hot plate. The piping should be a mini-
mum of 3/4" IPS supply pipe for a single hot plate.
A 3/4" NPT manual gas valve is shipped with each
single hot plate for fi eld installation. The required gas
pressure for proper operation of each hot plate is 4"
water column for natural gas and 10" water column
for Propane gas.
In-line pressure regulators are not supplied by
Keating. They are to be provided and installed by oth-
ers as directed by local codes.
NOTE: If more than one gas hot plate is on the same
supply line, you may require a larger line. Consult your
local gas company to assure adequate volume and
pressure. Refer to serial plate for proper gas require-
ments for your particular model.

ELECTRICAL CONNECTION

WARNING
The Keating hot plate with an option-
al spark ignitor is equipped with a 6'
neoprene covered, 3 wire electrical
cord with a three-pronged grounded
plug for protection against electrical
shock. This plug must be placed into
a 120V properly grounded three-
Plug into a
pronged outlet. For proper grounding
properly grounded
procedures see local codes or, in the
three-prong receptacle.
absence of local codes, the current
National Electrical Code ANSI/NFPA 70 or Canadian
Electrical Code CAN 22.1 as applicable.
4
|
keatingofchicago.com
NOTE: For hot plates with optional spark ignitors, the
electrical wiring diagram is located on the front of the
control panel. Hot plates with constant pilots do not
require any electrical connections.
DO NOT CUT OR REMOVE THE GROUNDING PRONG
FROM THIS PLUG.

GAS LEAK TESTING

Prior to lighting your hot plate:
1. Make sure all manual gas valves and gas valves
(infi nite controls) are in the "OFF" (fully clockwise)
position.
2. Turn main ON/OFF manual gas valve to the "ON"
position.
3. Have your plumber or gas company check for
leaks with a soap solution. (NEVER check with a
match!)
4. Have your plumber or gas company representa-
tive light the constant pilot. (Not necessary if your
hot plate has an optional spark ignitor.)
PROPANE GAS MAY EVENTUALLY LOSE ITS ODOR
AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE
THAT IT IS NOT PRESENT EVEN THOUGH YOU DO
NOT DETECT AN ODOR. IF THERE IS ANY DOUBT,
YOU SHOULD CALL YOUR LOCAL PROPANE GAS
SUPPLIER FOR ASSISTANCE.
OPERATING

LIGHTING

Keating hot plates are designed to provide maximum
effi ciency and deliver high quality food products.
Follow lighting procedure as listed.
OPERATION OF THIS HOT PLATE SHOULD BE LIMIT-
ED TO PERSONNEL WHO HAVE BEEN THOROUGHLY
TRAINED IN OPERATING PROCEDURES.
1. Open the manual gas valve.
2. For hot plates with constant pilots, light the con-
stant pilot (located between the front and rear burn-
ers) with a match. For hot plates with spark ignitors,
push in the red knob and rotate it fully counterclock-
wise unit the burner ignites.
For hot plates with spark ignitors, rotating the
red knob without holding it in may damage the
gas valve (infi nite switch).