PERFORMANCE DATA HEAT operation
MSZ-GB50VA : MUZ-GB50VA
CAPACITY:5.8(kW)
INPUT:1700(W)
INDOOR
-10
DB( : )
Q
INPUT
15
3.65
1105
21
3.48
1190
26
3.13
1275
NOTE Q : Total capacity (kW) INPUT : Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
9

ACTUATOR CONTROL

MUZ-GB50VA
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Compressor
Outdoor fan
motor
9-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
Compressor
R.V.coil
Outdoor fan
motor
at Rated frequency
OUTDOOR
-5
0
Q
INPUT
Q
INPUT
4.41
1326
5.16
1496
4.18
1411
4.93
1564
3.89
1496
4.58
1649
5 seconds
ON
OFF
ON
OFF
<COOL>
5 seconds
ON
OFF
ON
ON or OFF
OFF
ON
OFF
WB( : )
5
10
Q
INPUT
Q
INPUT
5.92
1615
6.67
1717
5.63
1683
6.38
1768
5.34
1768
6.09
1853
15 seconds
<HEAT>
5 seconds
ON or OFF
14
15
20
Q
INPUT
Q
INPUT
7.37
1768
8.12
1802
7.08
1819
7.80
1887
6.79
1904
7.54
1955