10

ACTUATOR CONTROL

MUZ-LN25VG
MUZ-LN35VG
MUZ-LN25VG2
MUZ-LN35VG2
10-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Compressor
Outdoor fan
motor
10-2. R.V. COIL CONTROL
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before startup of the compressor.
Compressor
10-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor
Discharge temperature
thermistor
Indoor coil temperature
thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature
thermistor
Outdoor heat exchanger tem-
perature thermistor
OBH767G
MUZ-LN50VG
MUZ-LN50VG2 MUZ-LN60VG2
5 seconds
ON
OFF
ON
OFF
<COOL>
ON
OFF
ON
R.V.coil
OFF
ON
Outdoor fan
OFF
motor
Purpose
Protection
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
Heating: Defrosting
Protection
Cooling: Low ambient tempera-
ture operation
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
MUZ-LN60VG
15 seconds
<HEAT>
5 seconds
Compressor
LEV
49
5 seconds
Actuator
Outdoor fan
Indoor fan
R.V. coil
motor
motor