Actuator Control - Mitsubishi Electric MUZ-EF25VG-E1 Service Manual

Hide thumbs Also See for MUZ-EF25VG-E1:
Table of Contents

Advertisement

10

ACTUATOR CONTROL

MUZ-EF25VG
MUZ-EF35VG
MUZ-EF25VGH MUZ-EF35VGH
10-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Compressor
Outdoor fan
motor
10-2. R.V. COIL CONTROL
Heating . . . . . . . . . . . . . . . . . ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
Compressor
10-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor
Discharge temperature
thermistor
Indoor coil temperature
thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature
thermistor
Outdoor heat exchanger tem-
perature thermistor
OBH832C
MUZ-EF42VG
5 seconds
ON
OFF
ON
OFF
<COOL>
ON
OFF
ON
R.V.coil
OFF
ON
Outdoor fan
OFF
motor
Purpose
Protection
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
Heating: Defrosting
Protection
Cooling: Low ambient tempera-
ture operation
Heating: Defrosting (Heater)
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
MUZ-EF50VG
15 seconds
<HEAT>
5 seconds
Compressor
LEV
33
5 seconds
Actuator
Outdoor fan
Indoor fan
R.V. coil
motor
motor
Defrost
heater

Advertisement

Table of Contents
loading

Table of Contents