Outside Air - - Up to 20% outside air can be introduced to the
40KMC or 40KMQ through pre- -punched knockouts.
If the 40KMC or 40KMQ is installed close to an outside wall,
some outside air can be introduced by running field supplied
ductwork to the unit.
the amount of outside air that can be
introduced is determined by using the chart in Fig. 9.
If the cassette is installed in the middle of a room and is not close to
an outside wall, a power ventilation kit can be used to overcome
the static pressure in the ductwork and allow the needed CFM.
For applications that are very sound sensitive, it is recommended to
limit the fresh air intake to 10% when using a power ventilation
kit.
Model
40KMC018--- --- --- 3
40KMC024--- --- --- 3
40KMC03036--- --- --- 3
40KMQ01824--- --- --- 3
40KMQ03036--- --- --- 3
* High Speed

SOUND RATINGS

Outdoor Units

Model Number
38HDF018--- --- --- 3
38HDF024--- --- --- 3
38HDF030--- --- --- 3
38HDF036--- --- --- 3/5/6
38QRF018--- --- --- 3
38QRF024--- --- --- 3
38QRF030--- --- --- 3
38QRF036--- --- --- 3/5/6

Indoor Units

Model Number
Sound Power
40KMC018--- --- --- 3
40KMC024--- --- --- 3
40KMC03036--- --- --- 3
40KMQ01824--- --- --- 3
40KMQ03036--- --- --- 3
NOTES: Tested in accordance with ARI Standard 270 --- --- ---95 and ARI 350 (no listed in ARI).
AIR THROW DATA*
4 Louvers Open
ft (m)
15.75 (4.8)
9.8 (3.0)
14.1 (4.3)
9.8 (3.0)
14.1 (4.3)
Sound Power dBA
66
66
72
72
66
66
72
72
High
Sound Pressure
dBA
dBA
55
44
49
38
58
47
49
38
58
47
Air Discharge - - The 40KMC and 40KMQ units have four
discharge outlets that are equipped with motorized louvers for
better comfort. The user has three operating choices with the
louvers
1. AUTO - - The position of the louver is determined by the
mode in which the unit is running.
2. CONTINUOUS - - Louvers move continuously
3. STATIONARY - - Louver position is determined by the
user.
Air can be discharged from 4, 3, or 2 louvers. An accessory kit is
required to block the discharge from each louver.
Air Throw Data - - The following table shows the air throw data of
the 40KMC and 40KMQ units. The numbers shown indicate the
maximum distances reached by the airflow with a speed equal to or
greater than .66 ft/sec (0.2 m/sec) with louvers in the cooling
position.
3 Louvers Open
ft (m)
17.4 (5.3)
11.5 (3.5)
15.75 (4.8)
11.5 (3.5)
15.75 (4.8)
Medium
Sound Power
Sound Pressure
dBA
dBA
51
40
45
34
55
44
45
34
55
44
30
2 Louvers Open
ft (m)
19.0 (5.8)
13.0 (4.0)
17.4 (5.3)
13.0 (4.0)
17.4 (5.3)
Sound Pressure dBA
55
55
61
61
55
55
61
61
Low
Sound Power
Sound Pressure
dBA
dBA
48
37
42
31
50
39
42
31
50
39