Operating Instructions Room controller Logamatic EMS For the user Please read carefully RC35 user interface before use.
Page 2
In automatic mode, an additional LED lights up with the “AUT” LED to indicate which operating status is currently active (“day mode” or “night mode”). The “domestic hot water” LED can also be disabled. Logamatic EMS RC35 user interface - Subject to technical modifications.
They are separated by lines above and below the text. Additional symbols Symbol Explanation Sequence of steps Cross-reference to other points in this document or to other documents • Listing/list entry – Listing/list entry (2nd level)) Tab. 1 Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 6
Note on using this manual: Section 5.1 "Introduction to the User menu" explains in detail the steps needed for programming all the settings in the Service menu. In the sections which come after it, programming is only exexplained in outline. Logamatic EMS RC35 user interface - Subject to technical modifications.
B In the event of a fault: remedy the fault immediately. Warning: device damage The RC35 has no field serviceable parts inside. Any attempt to open the housing will cause internal damage, render the device inoperable, and void the manufacturer's warranty.
Press the button. Change between: The modified room temperatures are day: 69°F saved. The LED next to the button night: 63°F lights up. Tab. 2 Getting started – room temperatures Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 9
In the case of large heating systems with multiple heating zones, note the following: The modifications in room temperature described above apply to all heating zones assigned to the RC35 user interface (these are the RC35 heating zones page 26).
Page 10
B To change the contrast: hold down the to change the contrast on the buttons and turn the dial display? at the same time. Tab. 3 Getting started – additional functions Logamatic EMS RC35 user interface - Subject to technical modifications.
Product description 3.1 Product description The RC35 user interface makes it easy to operate your Buderus heating system. You can set the room temperature for your entire home using the dial. The automatic mode with its adjustable programs ensures energy-saving operation by reducing the room temperature at certain times or shutting down heating completely (adjustable night setback).
Basic operation Basic operation 4.1 Display The display on the RC35 user interface presents the following elements during normal operation: 71 F Room please open cover 6 720 618 414-01.1RS Fig. 1 Elements on the display Top information row: standard display (factory setting: date and time)
The settings made using the buttons above apply to all heating zones assigned to the RC35 user interface (these are referred to as the “RC35 heating zones” page 26). To set the operating mode for other heating zones: use the User menu\modes of operation ( page 29).
The automatic program uses the temperatures normally set for day and night mode. -or- B To return to manual mode: press either The temperatures normally set for day or night mode will be used. Logamatic EMS RC35 user interface - Subject to technical modifications.
1) If “shut-down mode” is selected as the nighttime reduction mode, the heating system will be switched off at night. A night room temperature cannot be set. The display will show a message to that effect. Logamatic EMS RC35 user interface - Subject to technical modifications.
( page 27). No selection is possible if there is only one heating zone to choose from. All RC35 heating zones have the same room temperature settings. If no selection is possible or if you select RC35 heating zones, you will be setting the same temperatures as described on page 15.
3. Release the button. The hours are saved. 4. Repeat steps 1 to 3 to set the minutes. The set time is shown briefly. The standard display then re-appears. Logamatic EMS RC35 user interface - Subject to technical modifications.
The water in the hot water tank is “Aut” heated once in the morning for 30 minutes before home heating starts. Tab. 5 Setting functions for domestic hot water Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 19
Tab. 5 Setting functions for domestic hot water 1) The setting depends on the boiler used. 2) The “domestic hot water” LED may also have been deactivated by the heating contractor. Logamatic EMS RC35 user interface - Subject to technical modifications.
“0”. Set the dial to “Aut” . Set to allow water heating to be set from the RC35. The operating mode buttons have no function in the Info menu. 1) Setting depends on the boiler used. Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 21
The days in the current week which still have not passed are marked with “---”. At days where the solar yield could not be determined “0” is displayed. 1) This function depends on the boiler in use. Logamatic EMS RC35 user interface - Subject to technical modifications.
4.11 Shut-down/switching OFF The RC35 user interface is supplied with power via the heating system and is permanently switched on. It is only switched off if the heating system is switched off, such as for maintenance purposes.
USER MENU selected (marked with ). standard display modes of operation program WWSD temperature Tab. 7 How to use the User menu (example) Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 24
The standard display appears again. You can enter all settings in the USER MENU using this procedure. Tab. 7 How to use the User menu (example) Logamatic EMS RC35 user interface - Subject to technical modifications.
Heating up domestic hot water to kill potential pathogens disinfection corrected room Calibrate displayed room temperature with the help of a thermometer. tmp. Tab. 8 User menu 1) This function depends on the boiler in use. Logamatic EMS RC35 user interface - Subject to technical modifications.
Heating zones with mixing valve, i. e. with reducible flow temperature RC35 heating zones All heating zones assigned to the RC35, i.e. those that do not have their own remote control unit ( Fig. 2, [1]). Displayed only if more than one heating zone is assigned to the RC35.
Page 27
The supply temperature is the heating water temperature, generated by the boiler, as it is supplied to the heating zone. With the RC35 user interface, you can operate and control multiple heating zones ( Fig. 2). Fig. 2 Options for a heating system with two heating zones Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 28
1) Heating zone selection is not possible if there are no other heating zones available, such as DHW for example. 2) Here: setting by heating contractor HZ1 = RC35, HZ2 = none Logamatic EMS RC35 user interface - Subject to technical modifications.
– collector temperature (with solar heating systems only) 5.5 Selecting the operating mode 5.5.1 Operating modes for RC35 heating zones For the RC35 heating zones, the operating mode can be set directly by pressing the corresponding button (e.g. ). For other heating zones, use this menu item.
(collector protection function). For explanations of the settings, see the documentation for the solar module. 1) Menu is always displayed, the function depends on the boiler in use. Logamatic EMS RC35 user interface - Subject to technical modifications.
In the factory setting, the program also determines the times for DHW heating and the operation of the DHW i.e. circulation pump. However, you can also set separate programs for both functions ( sections 5.7 and 5.8). Logamatic EMS RC35 user interface - Subject to technical modifications.
Creating a new program: B Select new program. The enter switch point menu item ( page 36) opens automatically for you to create your program. Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 33
(22:00) afternoons only) 6:00 am 3:00 pm 11:00 pm (06:00) (15:00) (23:00) 6:00 am (06:00) 7:00 am (07:00) Tab. 11 Standard programs (ON = day mode, OFF = night mode) Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 34
You can save and later select two new or modified programs as custom 1 or custom 2. custom 1 Mo–Th custom 2 Mo–Th Tab. 11 Standard programs (ON = day mode, OFF = night mode) Logamatic EMS RC35 user interface - Subject to technical modifications.
Turn it further to go to a different day of the week. The selected switch point starts flashing. 2. Hold down the button and turn the dial to change the time for that switch point. Logamatic EMS RC35 user interface - Subject to technical modifications.
After that the switch point is saved. 4. Repeat steps 1 to 3 to enter other switch points. 5. Turn the dial to go to other days. 6. Press when you have finished making entries. Logamatic EMS RC35 user interface - Subject to technical modifications.
1 or custom 2 or select not saved to cancel. The selected program, custom 1 or custom 2, is used from now on for that heating zone. Logamatic EMS RC35 user interface - Subject to technical modifications.
• Heating zones without remote control ( page 54, setting “none”): different room temperatures are possible for each zone, in contrast to the RC35 heating zones. The room temperature is set as described below. • RC35 heating zones: the room temperatures are the same for all heating zones assigned to the RC35.
This ensures that hot water is available during the heating phases (i.e. when in day mode). If you want to enter a separate hot water program, Buderus recommends: • Heating the hot water tank only once in the morning before home heating starts.
B Make sure that a thermostatic mixing valve is installed and that it is set to temperatures below 122 °F (50 °C). Logamatic EMS RC35 user interface - Subject to technical modifications.
3. Select the heating zone to be switched over to vacation mode: – complete system: heating zones, water heating and DHW circulation. – RC35 heating zones: this option is only displayed if one or more heating zones are assigned to the RC35; DHW and the other heating zones remain active.
Page 42
The cover must be closed when you do so. If you want to exit the vacation mode early: B Open User menu\vacation again. B Answer the question Continue cancelling the vacation mode? with yes. Logamatic EMS RC35 user interface - Subject to technical modifications.
Page 43
2) No separate program was created for the recirculation pump, that is, the switching times of the recirculation pump and of the DHW program are the same. 3) The earliest switch-on point and latest switch-off point out of all heating zones on this day will apply. Logamatic EMS RC35 user interface - Subject to technical modifications.
The pause function is now active. When the time has expired, it will return to the automatic mode. Ending the pause function early: B Open USER MENU\pause function again and select end. Logamatic EMS RC35 user interface - Subject to technical modifications.
5.16 Calibrating the room temperature display If there is a separate thermometer near the RC35 when installed in the living space, it may show a different room temperature to that shown on the unit. If you wish to adjust the RC35 to match the thermometer (i.e.
Page 46
User menu A thermometer may indicate temperature fluctuations more slowly or rapidly than the RC35. B so never calibrate the RC35 when your heating system is in the process of cooling down or heating up. 1. Open the User menu.
• Room temperature control: in this case, the RC35 must be mounted in a room that is representative of your home. The RC35 records the room temperature in this “reference room”.
• Ventilate your home wisely: Leave the windows wide open for a few minutes rather than leaving them slightly open all the time. • While ventilating rooms, set the RC35 to night mode. Do this by pressing the night button.
Why does a separate thermometer not match the room temperature set in the RC35? Various different factors influence the room temperature. If the RC35 is installed on a cold wall, it will be influenced by the cold temperature of that wall. Conversely, it will be influenced by the heat from a fireplace or chimney, if it is installed in a warm part of the room.
Page 50
In the last two cases the boiler may run even if the recorded room temperature is higher than the set room temperature. Logamatic EMS RC35 user interface - Subject to technical modifications.
7.2 Error messages and service messages The RC35 makes a distinction between three types of messages: • Faults (in boiler operation) • System errors (incorrect settings on the RC35, or component malfunctions) • Service messages (indicating that servicing is due) Faults The display shows the following message: Your system has a fault present.
Page 52
A11/ Date not set. outage, for example. Tab. 13 Table with plant errors and service messages Logamatic EMS RC35 user interface - Subject to technical modifications.
For instructions on carrying out the reset function on the boiler control panel, see the technical documentation for the boiler. B If the fault cannot be reset (the display continues to flash), notify your heating contractor. Logamatic EMS RC35 user interface - Subject to technical modifications.
Heating zone 4 Tab. 14 Heating zone assignment 1) With the setting “none”, the heating zone can be controlled from the RC35, but is not included in the “RC35 heating zones” (room temperatures can therefore be set separately). 2) Not installed with several boilers.
Page 55
DHW priority yes, no Program Standard program name: (times page 31) custom program Tab. 15 Settings made during commissioning 1) This function depends on the boiler in use. Logamatic EMS RC35 user interface - Subject to technical modifications.