Mitsubishi Electric Mr.Slim MUZ-A09NA Service Manual page 51

Outdoor unit
Table of Contents

Advertisement

MUZ-A24 MUZ-GA24
Heating operation does not work.
1.
Disconnect the lead wire leading to the compressor.
2.
3 minutes after turning on the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 208/230 VAC between pin1
and pin 2 at connector CN912?
Yes
Turn OFF power supply of indoor and outdoor unit.
Disconnect the connec-
tor CN912 in noise fi lter
P.C. board. Is there normal
resistance to R.V. coil?
Yes
Replace the 4-way valve.
Cooling operation does not work.
1.
Disconnect the lead wire leading to the compressor.
2.
3 minutes after turning on the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 208/230 VAC between pin1
and pin 2 at connector CN912?
1.
Turn OFF power supply of indoor and outdoor unit, and
disconnect the connector CN781 in the outdoor electronic
control P.C. board.
2.
3 minutes after turning ON the power supply, start EMER-
GENCY OPERATION in COOL mode.
Is there voltage 12 VDC between the connector
CN781 pin 5 (+) and pin 3 (-)?
Replace the outdoor electronic control P.C. board.
Replace the R.V. coil.
No
Yes
1.
Turn off power supply of indoor and outdoor unit, and discon-
No
nect the connector CN781 in the outdoor electronic control P.C.
board.
2.
3 minutes after turning ON the power supply, start EMER-
GENCY OPERATION in HEAT mode.
Is there voltage 12 VDC be-
tween the connector CN781
pin 5 (+) and pin 3 (-)?
Replace the noise fi lter P.C. board.
Replace the 4-way valve.
No
Replace the noise fi lter P.C. board.
No
51
Replace the electronic
No
control P.C. board.
Yes
If the connector CN912 is disconnected or R.V.
coil is open, voltage occurs between terminals
even when the control is OFF.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents