Heat & Glo RED60 Owner's Manual page 42

Installation and operation
Hide thumbs Also See for RED60:
Table of Contents

Advertisement

1. Follow safety inspection procedures recommended by
national, provincial, and/or local codes.
2. Be certain all electrical connections are properly made
and secure.
3. Visually inspect the vent system and determine that
there is no fl ue gas spillage, blockage or restriction,
leakage, corrosion or other unsafe defi ciencies.
4. Place the fi replace in operation and determine that the
burner and power vent are operating properly. The
main burner should show no signs of fl oating, lifting, or
fl ashbacks.
WARNING:
If any unsafe condition is determined when
inspecting the installation and operation of the fi replace
and Power Vent, the equipment should be shut off. Cor-
rections MUST be made before the equipment is put into
continuous operation.
SETTING THE EXHAUST CONTROL
The PVK-80 has an exhaust control lever which must be
set and secured during the Installation Inspection. The
lever is located behind the electrical cable connector of
the cap housing and is factory set in the closed position.
See Figure 7.39.
Figure 7.39
The exhaust control lever must remain in the closed po-
sition for optimum appliance performance. Secure the
exhaust control lever to the power vent housing with the
sheet metal screw. Do not change this setting.
WARNING! Risk of Overheating! DO NOT change ex-
haust control lever setting! Glass failure will occur.
42
CONTROL LEVER -
REMOVE SCREW
TO ADJUST
SECURE CONTROL
LEVER WITH SCREW
AFTER ADJUSTMENT
Heat & Glo • RED60 • 2159-900 Rev. B • 12/09
OPERATING INSTRUCTIONS
After installation of the power vent, follow the operation
instructions of the fi replace.
1. Turn the fi replace ON/OFF switch to "ON".
NOTE
: During periods of operation after turning the fi re-
place "ON", there may be a slight delay before the fi replace
ignites. This is due to the time necessary for the fan to
reach operating speed and to remove any gases from the
combustion chamber.
2. After turning the switch to the "ON" position, if the fi re-
place does not turn on, shut the switch to "OFF" and
inspect the power vent system for any debris that may
be obstructing the fan blade movement.
3. Turn the fi replace ON/OFF switch to "OFF" to turn off
the burner and the power vent.
MAINTENANCE
CAUTION
: Before performing any maintenance or repair
to the power vent assembly, make sure electrical power is
disconnected to the fi replace.
1. Vent System: Inspect all components and connections
annually. Replace, seal, or tighten pipe connections if
necessary.
2. Power Vent Cap: Inspect at least annually, to clear
away any debris blocking any part of the cap.
3. Motor: The fan motor bearings are sealed and no further
lubrication is necessary.