Napoleon BGD36CFNTR Installation And Operating Instructions Manual page 17

Napoleon gas fireplaces - installation and operating instructions

Advertisement

bGD42CF HORIzONTAL TERMINATION
when (H
) > (V
)
T
T
Simple venting configuration (only one 45º and 90° elbow)
See graph to determine
the required vertical rise
V
for the required hori-
T
zontal run H
.
T
FIGURE 31
required
vertical
rise in
inches
V
T
horizontal vent run Plus offsets in feet
(h
)
t
The shaded area within the lines represents acceptable
values for H
and V
.
T
T
For vent configurations requiring more than one 45º and
one 90° elbow the following formulas apply:
Formula 1: HT < 4.2 VT
Formula 2: HT + VT < 24.75 feet
Example 2:
H
45°
V
1
V
= 4 ft
1
V
= .5 ft
2
V
= V
+ V
= 4 + .5 = 5.5 ft
T
1
2
H
=  ft
1
H
=  ft
2
H
=  ft
3
H
= .5 ft
4
H
= H
+ H
+ H
+ H
R
1
2
3
H
= .0(one 450° elbow + three 90° elbows - 5°)
O
= .0(5 - 5) = 5.4 ft
H
= H
+ H
= 5.5 + 5.4 = 0.9 ft
T
R
O
H
+ V
= 0.9 + 5.5 = 6.4 ft
T
T
H
< 4.2V
Formula :
T
4.V
T
0.9 < 6.8
H
+ V
< 24.75 feet
Formula :
T
T
6.4 < 4.75
Since both formulas are met, this vent configuration is
acceptable.
90°
90°
H
1
3
V
2
H
90°
2
FIGURE 32
=  +  +  + .5 = 5.5 ft
4
T
= 4. x 5.5 = . ft