Connect Gas Supply Line; Burner Information - Vermont Castings RADVTCB Homeowner's Installation And Operating Manual

Radvt series, radvtcs series direct vent gas heaters
Table of Contents

Advertisement

Radiance
®
Direct Vent Gas Heater
Figure 51
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the
firebox, to confirm that you have the appropriate firebox
for the type of fuel to be used. The Radiance may be con-
verted from one gas to another using the appropriate Fuel
Conversion Kit listed on Page 46.
In the U.S.; Gas connection should be made in accordance
with current National Fuel Gas Code, ANSI Z3.1/NFPA
54. Since some municipalities have additional local codes,
be sure to consult your local authority.
In Canada; consult the local authority and CSA-B149.1
installation code.
Always check for gas leaks with a mild soap
and water solution. Do not use an open flame
for leak testing.
Light the pilot according to the directions on Page 31,
before going to the next step.

Burner Information

The appliance must only use the gas specified on the rat-
ing plate, unless converted using a Vermont Castings Fuel
Conversion Kit. To convert from Natural Gas to LP use Kit
00179 or 001900. To convert from LP to Natural Gas
use Kit 001899 or 00190.
Conversion instructions are provided with each kit and
beginning on Page 37 in this manual.
88
Left Cross
Rear Log
Log
Front Left Log
Ember Bed
CAUTION
This appliance should only be connected
by a qualified gas technician. Test to
confirm manifold pressures as specified
below.
The Radiance Heater and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.5 kPa).
The Radiance Heater must be isolated from the
gas supply piping system by closing its individual
manual shutoff valve during any pressure testing
of the gas supply piping system at test pressure
equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and
the supply.
In order to connect Natural Gas, use a fitting with
1/2" NPT on the valve side and 1/2" natural gas sup-
ply line with an input of 38,000 BTUs at a manifold
pressure of 3.5" between minimum inlet supply of
5.5" w.c. and maximum of 14.0" w.c.
In order to connect Propane, use a fitting with 1/2"
NPT on the valve side and 1/2" propane gas supply
line with an input of 36,000 BTUs at a manifold pres-
sure of 10.0" between a minimum inlet supply of 11.0"
w.c. and maximum of 14.0" w.c.
Right Cross Log
Front Right Log
LG490
30004967