MHG Heating ProCon 16 Installation And Operating Manual page 55

Wall mounted condensing boiler range
Table of Contents

Advertisement

16.1 RVA47 Cascade Manager Settings.
The Single and Cascade Master units are preset for correct operation.
The following Pages detail the parameters of the RVA47 Cascade Manager and the Standard Factory
settings, please note, the installer/commissioning engineer may have changed some of these settings
to suit the system installed.
There are two levels of access available, as follows. If you cannot access a particular parameter line,
please consult with MHG's Technical Department for further assistance.
Level One
-
Open The Hinged Flap.
(End User)
Use either of the
line. (Parameter Line range 0-50)
Use the
Once all alterations have been completed press the AUTO button to exist this
level.
Level Two
-
Open The Hinged Flap.
(Installer)
Press & Hold the
seconds until Parameter # 51 appears.
Use either of the
line. (Parameter Line range 51-173)
Use the
Once all alterations have been completed press the AUTO button to exist this
level.
Level Three
-
Open The Hinged Flap.
(OEM)
Press & Hold the
until - - - - - appears.
A password will be required to access this level.
(Down Down Plus Minus Plus)
Use either of the
line. (Parameter Line range 2-92)
Use the
Once all alterations have been completed press the AUTO button to exist this
level.
Complete RVA47 Cascade Controller Parameter Settings.
The defaults indicated on the following pages are for standard systems.
If additional control features are required alteration will have to be made.
Please refer to the RVA47 manual for additional details.
#, -, ---
Indicates where an input can be made if required.
--
Indicates where an input can not be made and a sensed / attenuated figure is
displayed. 'OFF' will be displayed if the +/- buttons are used.
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email
© MHG Heating Ltd
Program Buttons to access the desired parameter
Buttons to alter the required parameter.
Program Buttons simultaneously for more than 3
Program Buttons to access the desired parameter
Buttons to alter the required parameter.
Program Buttons simultaneously for up to 9 seconds
Program Buttons to access the desired parameter
Buttons to alter the required parameter.
info@mhgheating.co.uk
010109
Web www.mhgheating.co.uk
55

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProCon 16 and is the answer not in the manual?

This manual is also suitable for:

Procon 27Procon 47Procon 75Procon 77

Table of Contents