Physical And Electrical Data - Coleman HC6B024 THRU 060 Technical Manual

Echelon series split-system heat pumps 16 seer – r-410a – 1 phase 2 thru 5 nominal tons

Advertisement

632152-CTG-E-0812

Physical and Electrical Data

Model
Unit Supply Voltage
1
Normal Voltage Range
Minimum Circuit Ampacity
Max. Overcurrent Device Amps
Min. Overcurrent Device Amps
Compressor Type
Rated Load
Compressor Amps
Locked Rotor
Crankcase Heater
Factory External Discharge Muffler
Factory External Check Valve
4
HS Kit Required with TXV
Fan Motor Amps
Rated Load
Fan Diameter Inches
Rated HP
Fan Motor
Nominal RPM
Nominal CFM
Face Area Sq. Ft.
Coil
Rows Deep
Fins / Inch
Liquid Line Set OD (Field Installed)
Vapor Line Set OD (Field Installed)
5
Unit Charge (Lbs. - Oz.)
Charge Per Foot, Oz.
Operating Weight Lbs.
1. Rated in accordance with AHRI Standard 110-2012, utilization range "A".
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.
5. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or
subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
A
VAPOR
3-1/8
6-1/2
LIQUID
2-3/8
2
HC6B024F3(C) HC6B030F3(C) HC6B036F3(C) HC6B042F4(C) HC6B048F3(C) HC6B060F3(C)
17.5
2
30
3
20
Scroll
13.4
58.3
No
Yes
No
No
0.7
24
1/8
1075
2750
20.6
1
22
3/8
3/4
9 - 3
0.68
199
B
C
208-230V, 1 60Hz
187 to 252
17.3
22.6
30
35
20
25
Scroll
Scroll
12.8
17
64
77
No
No
Yes
Yes
No
No
No
No
1.3
1.3
24
24
1/4
1/4
850
850
3800
3800
23.6
23.6
1
1
22
22
3/8
3/8
3/4
3/4
9 - 13
10 - 10
0.68
0.68
228
230
Unit
Model
A
024
40
030
40
036
40
042
40
048
40
060
40
* Adapter fitting required for 1-1/8" line set.
Overall height is from bottom of base pan to top of fan guard.
Overall length and width include screw heads.
23.7
26.9
40
45
25
30
Scroll
Scroll
17.9
20.5
112
115
No
No
Yes
Yes
No
No
No
No
1.3
1.3
24
24
1/4
1/4
850
850
3800
3400
23.6
23.6
1
2
22
22
3/8
3/8
7/8
7/8
11 - 7
14 - 5
0.70
0.70
237
283
Dimensions
Refrigerant Connection
(Inches)
Service Valve Size
B
C
Liquid
37
31
42-1/4
34
42-1/4
34
3/8
42-1/4
34
42-1/4
34
42-1/4
34
Johnson Controls Unitary Products
33.8
50
35
2-Stage Scroll
26
118
No
Yes
No
No
1.3
24
1/4
850
3700
23.6
2
14
3/8
1-1/8
14 - 11
0.76
298
Vapor
3/4
7/8
7/8*