Interconnection
Note:
Installation should only be performed by qualified personnel and in
accordance with local governing regulations.
Recommendations
When using an XPS 15 F transducer, configure the electronic transceiver for
an XCT-12. These two transducers use the same settings.
Do not route cable openly.
For optimum isolation against electrical noise, run cable separately in a
grounded metal conduit.
Seal all thread connections to prevent ingress of moisture.
Do not run cable near high voltage or current runs, contactors and SCR
control drives.
Note:
In the interconnection examples that follow:
an XPS 10 F Series transducer is shown. An XPS 15 F transducer can
also be used, but no hazardous seal is required.
assume that the transducer is located in a Hazardous location (Class I,
Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G.) and the
transceiver in a Non-Hazardous (Safe) Location.
Direct Connection
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
metal conduit
A5E32725813
(XPS 10 F shown)
Non-Hazardous Location
Note:
When connecting to SITRANS LUT400, SITRANS LUC500,
MultiRanger 100/200, or HydroRanger 200, the white,
black, and shield wires are all connected separately. DO
NOT tie the white and shield wires together.
XPS 10/15 F Series Transducer
(Safe)
blk
wht
drain / shield