Mitsubishi Electric PUHZ-HRP71VHA Service Manual page 72

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-HRP71VHA:
Table of Contents

Advertisement

SW2 setting
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Outdoor pipe temperature / Cond./ Eva.
(TH6)
ON
-39~88
1
2 3 4 5 6
Outdoor outside temperature (TH7)
-39~88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8)
-40~200
ON
1
2 3 4 5 6
Discharge superheat SHd
0~255
ON
Cooling = TH4-TH6
1
2 3 4 5 6
Heating = TH4-TH5
Sub cool. SC
0~130
ON
Cooling = TH6-TH3
1
2 3 4 5 6
Heating = TH5-TH4
Input current of outdoor unit
ON
1
2 3 4 5 6
LEV-B opening pulse
0~480
ON
1
2 3 4 5 6
Targeted operation frequency
0~255
ON
1
2 3 4 5 6
DC bus voltage
180~370
ON
1
2 3 4 5 6
Display detail
Explanation for display
17~30
-39~88
(When the temperature is 0
temperature are displayed by turns.)
-39~88
(When the temperature is 0
temperature are displayed by turns.)
-40~200
(When the temperature is 0
temperature are displayed by turns.)
(When the thermistor detects 100
hundreds digit, tens digit and ones digit are
displayed by turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
180~370
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
72
Unit
or less, "–" and
or less, "–" and
or less, "–" and
or more,
0.1 A
Pulse
°C
°C
Hz
V