This manual contains important instructions for models LP 33U Series / 50 & 60 kVA that should
be followed during installation and maintenance of the UPS and battery.
-
Move the UPS in an upright position in its original package to the final destination
room.
-
Check for sufficient floor and elevator loading capacity.
-
Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS. Contact the nearest Service
Center immediately.
-
WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user
serviceable parts inside.
-
After switching off takes 5 minutes for the DC capacitors to discharge because a
lethally high voltage remains at the terminals of the electrolytic capacitors.
-
All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
-
The field-wiring terminals may be electrically live, even when the UPS is disconnected
from the utility.
-
Dangerous voltages may be present during battery operation.
The battery must be disconnected during maintenance or service work.
-
This UPS contains potentially hazardous voltages.
-
Be aware that the inverter can restart automatically after the utility voltage is restored.
-
Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to
131°F (55°C).
-
If the unit is stored for a period exceeding 3 months, the battery must be recharged
periodically (time depending on storage temperature).
-
The battery-voltage is dangerous for person's safety.
When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
-
All the battery used, shall be of the same manufacturer and date of production.
-
Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
-
Never dispose of battery in a fire: They may explode.
-
Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
-
Avoid charging in a sealed container.
-
Never short circuit battery. When working with battery, remove watches, rings or other
metal objects, and only use insulated tools.
-
In case of air shipment, the cables +/- going to the battery fuses/terminals shall be
disconnected and isolated.