Vitocom 300, Type Fa5, Fi2, Gp2 - Viessmann VITOCAL 300-G Technical Manual

Brine/water and water/water heat pump single and two-stage, from 21 kw
Table of Contents

Advertisement

Heat pump control unit
On-site requirements:
Good reception for GSM communication of the selected mobile phone
operator.
Total length of all KM BUS subscriber cables up to 50 m.
0
7 2
1 3
Specification
Rated voltage
Rated frequency

Vitocom 300, type FA5, FI2, GP2

Part no: see current pricelist
■ Type FA5 with integral analogue modem
■ Type FI2 with integral ISDN modem
■ Type GP2 with integral GPRS modem
■ For up to 5 heating systems with one or more heat sources, with or
without heating circuits downstream.
In conjunction with Vitodata 300
■ For remote reporting, remote monitoring and scanning of faults and/
4
or data points via the internet
■ For remote switching, remote setting of parameters and codes for
heating systems via the internet
Configuration
The Vitocom 300 is configured via the Vitodata 300.
Fault messages
Fault messages are reported to the Vitodata 300 server. These mes-
sages are transmitted via the following communication services from
the Vitodata 300 server to the configured control devices:
■ Fax
■ Text messages (SMS) to mobile phones
■ Email to PC/laptop
On-site requirements:
■ Telephone connection
– Type FA5:
TAE socket, coding "6N"
– Type FI2:
RJ45 socket (ISDN)
■ Type GP2:
Adequate GPRS radio signal for the D2 [Vodafone] mobile network
at the location where the Vitocom 300 is installed
■ LON communication module must be installed in the Vitotronic appli-
ance
Note
For further information regarding the terms of contract, see the
Viessmann pricelist.
Mounting rail installation TS35 to DIN EN 50 022, 35 x 15 and 35 x 7.5.
*3
VIESMANN
68
(cont.)
230 V ~
50 Hz
Rated current
Power consumption
Protection class
Protection
Function
Permissible ambient temperature
– during operation
– during storage and transport
On-site connection
Fault input DE 1
Standard delivery:
■ Standard module
*3
(with 8 digital inputs, 1 digital output and 2 ana-
logue sensor inputs)
– Type FA5:
with integral analogue modem,
Connecting cable for telephone socket TAE 6N, 2 m long
– Type FI2:
with integral ISDN modem,
Connecting cable with RJ45 plug for ISDN socket, 3 m long
– Type GP2:
with integral GPRS modem,
Aerial with connecting cable, 3 m long
SIM card
■ LON connecting cable RJ45 – RJ45, 7 m long, for data exchange
between the Vitotronic and Vitocom 300
■ Power supply unit
*3
■ Power cable from the power supply unit to the standard module
Note
For standard delivery of packs with Vitocom, see pricelist.
Accessories:
Accessories
Wall mounting enclosure for the installation of the
Vitocom 300 module, if no control panel or electrical
distribution panel is available
2 rows
3 rows
*3
Extension module
– 10 digital inputs (8 zero volt, two 230 V~)
– 7 analogue inputs (2 can be configured as pulsed
inputs)
– 2 digital outputs
– see the standard module for dimensions
or
– 10 digital inputs (8 zero volt, two 230 V~)
– 7 analogue inputs (2 can be configured as pulsed
inputs)
– 2 digital outputs
– 1 M BUS interface with connection of up to, for exam-
ple, 16 M BUS capable heat meters with M BUS slave
interface to EN 1434-3
– see the standard module for dimensions
Uninterruptible power supply unit
15 mA
4 W
II
IP 41 to EN 60529; safeguard
through appropriate design
and installation
Type 1B to EN 60 730-1
0 to +55 °C
Installation in living spaces or
boiler rooms (standard ambi-
ent conditions)
-20 to +85 °C
230 V~
Part no.
7143 434
7143 435
7143 431
7159 767
7143 432
*3
(UPS)
VITOCAL 300-G