EQUIPMENT DATA for brine-to-water heat pumps for heating purposes
1
TYPE AND COMMERCIAL DESCRIPTIONS
2
MODEL
2.1
Type
2.2
Enclosure type acc. to EN 60 529
2.3
Installation site
3
PERFORMANCE DATA
3.1
Operating temperature limits:
Heating water supply
Cooling, supply
Brine (heat source, heating)
Brine (heat sink, cooling)
Antifreeze agent
Minimum brine concentration (-13°C freezing temperature)
3.2
Heating water temperature spread at B0 / W35
3.3
Heating capacity/coeff. of perform.
3.4
Cooling capacity, coeff. of perform.
3.5
Sound power level
3.6
Heating water flow rate at internal pressure difference
3.7
Brine flow rate at internal pressure difference (heat source)
3.8
Refrigerant; total charge weight
DIMENSIONS, CONNECTIONS AND WEIGHT
4
4.1
Equipment dimensions without connections
4.2
Equipment connections for heating system
4.3
Equipment connections for heat source
4.4
Weight of transport unit(s) incl. packaging
5
ELECTRICAL CONNECTION
5.1
Nominal voltage; fusing
5.2
Nominal power consumption
5.3
Starting current with soft starter
Nominal current B0 W35 / cosϕ
5.4
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
7
OTHER DESIGN CHARACTERISTICS
7.1
Water inside equipment protected against freezing
7.2
Performance settings
7.3
Controller internal / external
These data characterize the size and performance capability of the system. For economic and energetic reasons, additional
1)
factors such as balance point and control need to be taken into consideration. Abbreviations have the following meaning, e.g. B10 /
W55: heat source temperature 10 °C and heating water supply temperature 55 °C.
2)
The heating circulating pump and the controller of the heat pump must be ready for operation at all times.
3)
See EC Declaration of Conformity
4)
Please keep in mind that more space is required for pipe connection, operation and maintenance.
Subject to technical modifications
°C
°C
°C
°C
K
at B-5 / W55
kW / ---
1)
at B0 / W50
kW / ---
1)
at B0 / W35
kW / ---
1)
at B20 / W8
kW / ---
at B20 / W18
kW / ---
at B10 / W8
kW / ---
at B10 / W18
kW / ---
dB(A)
m³/h / Pa
m³/h / Pa
Type / kg
H x W x L mm
4)
inches
inches
kg
V / A
B0 W35
kW
1)
A
A / ---
2)
..5MSR
..7MSR
reversible
reversible
IP 20
IP 20
indoors
indoors
max. 55
max. 55
+8 to +20
+8 to +20
-5 to +25
-5 to +25
+5 to +25
+5 to +25
monoethylene glycol monoethylene glycol monoethylene glycol monoethylene glycol
0,25
0,25
9,4
9,1
4,0 / 2,0
5,4 / 2,1
4,8 / 2,7
6,2 / 2,7
4,9 / 3,9
6,4 / 3,8
5,4 / 4,6
7,0 / 4,5
6,6 / 5,3
8,6 / 5,3
5,4 / 5,6
7,0 / 5,5
6,8 / 6,7
8,8 / 6,6
54
55
0,45 / 1900
0,6 / 3300
1,2 / 16000
1,7 / 29500
R407C / 0,9
R407C / 0,9
800 × 600 × 450
800 × 600 × 450
1¼" ext. thread
1¼" ext. thread
1¼" ext. thread
1¼" ext. thread
101
104
230 / 16
230 / 16
1,25
1,68
24
26
6,8 / 0,8
9,1 / 0,8
3)
3)
yes
yes
1
1
internal
internal
Issued: 14.04.2004
12
..9MSR
..11MSR
reversible
reversible
IP 20
IP 20
indoors
indoors
max. 55
max. 55
+8 to +20
+8 to +20
-5 to +25
-5 to +25
+5 to +25
+5 to +25
0,25
0,25
10,6
9,9
7,5 / 2,0
9,8 / 2,1
8,8 / 2,8
11,3 / 2,9
9,3 / 4,0
11,6 / 4,1
9,9 / 4,6
11,4 / 4,6
12,0 / 5,4
14,1 / 5,3
9,9 / 5,6
11,6 / 5,7
12,4 / 6,7
14,1 / 6,5
56
56
0,75 / 2300
1,0 / 4100
2,3 / 25000
3,0 / 24000
R407C / 1,25
R407C / 1,6
800 × 600 × 450
800 × 600 × 450
1¼" ext. thread
1¼" ext. thread
1¼" ext. thread
1¼" ext. thread
110
114
230 / 20
230 / 25
2,3
2,8
38
38
12,5 / 0,8
15,2 / 0,8
3)
3)
yes
yes
1
1
internal
internal