SECTION XIII: INSTALLATION FOR POTABLE WATER AND SPACE HEATING
GAS WATER HEATERS SUITABLE FOR WATER (POTABLE) HEATING AND SPACE HEATING
1. All piping components connected to this water heater for space-heating applications must be suitable for use with
potable water. In Massachusetts, space heating piping must not exceed 50 feet.
2. Toxic chemicals, such as those used for boiler treatment, must not be introduced into potable water used for space
heating.
3. This water heater must not be connected to an existing heating system or component(s) previously used with a non-
potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than required for other uses, such as an
ASSE approved mixing valve must be installed to temper the water for those uses in order to reduce the scald hazard
potential.
Please refer to the illustrations below and on the following pages for suggested piping arrangements.
Suggested Piping Arrangement For Side Connections
THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF:
Suggested Piping Arrangement For Top Connections
Suggested Piping Arrangement For Top and Side Connections