DCA-25USIXF/DCA-25USI2XF— OUTPUT TERMINAL PANEL
Connecting Loads
Loads can be connected to the generator by the UVWO terminal
lugs or the convienience receptacles. (See Figure 13). Make
sure to read the operation manual before attempting to connect
a load to the generator.
To protect the UVWO output terminals from overload, a 3-pole,
60 amp, main circuit breaker is provided. Make sure to switch
ALL circuit breakers to the "OFF" position prior to starting the
engine.
Figure 13. Connecting Loads
PAGE 24 — DCA-25USIXF/DCA-25USI2XF — OPERATION AND PARTS MANUAL — REV. #8 (05/08/09)
Over Current Relay
An over current relay (Figure 14) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the reset button on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 14. Over Current Relay
DANGER - ELECTROCUTION HAZARDS
This fuse has current running through it any time the engine
is running. This fuse is NOT connected to the main circuit
breaker of the generator. Attempting to replace the fuse
with the engine and/or generator operating
could result in electrocution and severe
bodily harm . ALWAYS turn the unit
completely off before attempting to replace
or handle this fuse.