Honeywell W7761A Owner's Manual page 54

Excel 10 remote input/output device, excel 5000 open system
Table of Contents

Advertisement

Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Calibrate (C), Monitor (M),
Parameter (P), Schematic (S)
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH
MA
DA
EV
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
X
X
X
M
Table C1. Input/Output Points (Right Continued).
HW
MN
TS
SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.
DI2State:
Refer to the description for DI1State.
SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.
DI3State:
Refer to the description for DI1State.
SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.
DI4State:
Refer to the description for DI1State.
SrcHumidAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for humidity sensor was made via ncirioIoSelect
for AI5.
SrcHumidAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for humidity sensor was made via ncirioIoSelect
for AI6.
SrcPressAI5 is an output network variable corresponding to the voltage or current
input channel (AI5) if the selection for a pressure sensor was made via
ncirioIoSelect for AI5.
SrcPressAI6 is an output network variable corresponding to the voltage or current
input channel (AI6) if the selection for a pressure sensor was made via
ncirioIoSelect for AI6.
SrcTempAI1 is an output network variable corresponding to the analog input
channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1
applied to it.
SrcTempAI2 is an output network variable corresponding to the analog input
channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2
applied to it.
SrcTempAI3 is an output network variable corresponding to the analog input
channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3
applied to it.
SrcTempAI4 is an output network variable corresponding to the analog input
channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4
applied to it.
SrcVoltageAI is an output network variable corresponding to the voltage or current
input channel (AI5 or AI6) if the selection for a voltage sensor was made via
ncirioIoSelect.
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Comments
54
74-2699

Hide quick links:

Advertisement

Table of Contents
loading