Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in
the Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
E-Vision Enumerated Name in the Input
RA_Hum_C7600C
OA_Hum_C7600C
Filter_Diff_Pres
RA_Hum_C7600B
OA_Hum_C7600B
RA_Enthalpy
OA_Enthalpy
Space_CO2
Voltage_Monitor

ADDING DIGITAL INPUTS

See Table A-2 for the supported Digital input types that can be connected to the RIO Device. The user must add a software
point (pseudo digital nstate - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the
Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should
be followed. The user will add a Pseudo Digital nstate point (< Vd >) in step one instead of the Pseudo Analog to the RIO CARE
Plant and then use the Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the
E-Bus, that are used in Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
E-Vision Enumerated Name in the Input
Digital Input 1:
Active_Short / Active_Open
Digital Input 2:
Active_Short / Active_Open
Digital Input 3:
Active_Short / Active_Open
Digital Input 4:
Active_Short / Active_Open

ADDING DIGITAL OUTPUTS

See Table A-3 for the supported digital output types that can be connected to the RIO Device.
The user must add a software point (pseudo analog) that can be mapped to the actual hardware output through the Custom
Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom
Mapping function so that the Digital Output can be used in the Zone Manager control strategy or switching logic, or be used
with Excel 5000 controllers on the C-Bus.
1. With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the
pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to
add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point.
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into
switching logic. Select the Software Points menu item and then Pseudo Analog . The Create/Select Software Point < Va >
dialog box will be displayed. Type in a New point name for the Digital Output (such as MiscExhFan ) and click on the OK
button. The new point that was just created will be added to the screen as the header point for switching logic table and
also added to the Point list. Select the Cancel button to exit the Create/Select Software Point < Va > dialog box. Exit
switching logic by selecting the File menu item and Exit . CARE will display the Delete Unused Software Points list box.
Click the Cancel button to continue.
2. Go into the Data Point Editor ( Controller/Edit/Data Point Editor ) and under Point select the pseudo analog point that was
just created and the OK button. Select the drop down list for the Engineering Unit and scroll through the list until the Pct
engineering units are displayed. Select the Pct engineering unit that is shown with one decimal place (number 55) and
the OK button to save the selection. Cancel the User Address list box and select File/Exit to exit out of the Data Point
Editor .
3. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the Project and Export to E-
Vision menu items. Type in the name of the Zone Manager Export file when the Export Zone Manager dialog box is
Table A-1. Supported Voltage And Current Input Sensors.
Application Selection Tab

Table A-2. Supported Digital Input Types.

Application Selection Tab
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
RIO Network Variable that contains the
Hardware Input Value
Humidity1 or Humidity2
Humidity1 or Humidity2
Pressure1 or Pressure2
Humidity1 or Humidity2
Humidity1 or Humidity2
CurrentAI
CurrentAI
CO2Level
VoltageAI
RIO Network Variable that contains the
Hardware Input Value
SrcDigIn1Sts
SrcDigIn2Sts
SrcDigIn3Sts
SrcDigIn4Sts
41
74-2699