T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Installer Setup
Number
(Press Unoccupied
Select
Temp to change)
Extended fan
19
a
operation in heat
(T7300F only).
Extended fan
20
operation in
cooling
(T7300F only).
Fan key
21
adjustment
(models with Fan
key).
Remote sensing.
22
Temperature
23
b
averaging network
(T7300F only).
Not used.
24
Keypad lockout
25
level (keypad
lockout enabled/
disabled by DIP
switch 1 on
thermostat back).
(T7300F only)
Duration of
26
temporary
override.
Not used.
27 through 29
Deadband
30
(T7300F only).
Interstage control
31
point (T7300F,
Q7300C,D only).
Minimum on- time
32
(T7300F).
Minimum
33
compressor off-
time.
Temperature heat
34
range stops
(T7300F).
Temperature
35
cooling range
stops (T7300F).
Not used.
36
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
63-4355—4
Table 7. Thermostat Installer Setup Options. (Continued)
Factory Setting
Display
Description
0
No extended fan operation after
call for heat ends.
0
No extended fan operation after
the call for cooling ends.
0
Fan setting key operational.
0
Remote sensing not activated.
0
Temperature averaging disabled.
0
No lockout.
3
3: Three hour override.
2
Heating and cooling setpoints can
be set no closer than 2°F (1.1°C).
0
Disabled.
2
2-minute minimum on- time for
heating and cooling.
4
4-minute minimum compressor
off-time.
90
Highest heat setpoint.
45
Lowest cooling setpoint.
12
Other Choices
(Press
or
to change)
Display
Description
1
Fan operation extended 90 sec after call for
heat ends.
1
Fan operation is extended 90 seconds after
the call for cooling ends.
1
Fan setting key is Auto only.
1
Remote sensing activated.
1
Temperature averaging between local
sensor and remote sensor(s) activated.
1, 2 or 3 1: Lockout all thermostat keys except
system and fan settings, temporary
setpoint, clock and day adjustments,
increase
and decrease
2: Lockout all keys except Set Current Day/
Time, increase
and decrease
3: Lockout all keys except Temporary
Occupied and Set Current Day/Time (for
clock, day adjustment).
1, 8 or
1: One hour override.
12
8: Eight hour override.
12: Twelve hour override.
3 - 10
Heating and cooling setpoints can be set no
closer than the chosen value.
1 - 12
Temperature must change more than
chosen value before system calls for next
stage. (Example: heat setpoint: 68°F (20°C),
interstage setting: 2°F (1.1°C), temperature
is 65.5°F (18.5°C). Second stage turns on,
brings temperature to 66°F (19°C) and turns
off. Heat pump continues to run until setpoint
is reached.
0 or 1
No minimum on-time or 1-minute minimum
on-time for heating and cooling.
0, 1, 2, 3
Minimum number of minutes (0 through 5)
or 5
compressor is off between compressor calls.
40 to 89 Heat setpoint temperature range (1°F
increments).
46 to 99 Temperature range (1°F increments) for
cooling setpoint.
Actual
Setting
.
.