Honeywell T7200D Product Data page 11

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
CAUTION
Possible Equipment Damage.
Fan must be running when system is operating.
Heat pump and electric heat systems must be
configured correctly in Installer Setup 2 to prevent
equipment damage caused by the system running
without the fan.
Installer Setup
Number
(Press Unoccupied
Select
Temp to change)
Not used
1
a
2
Fan operation
Output stages of
3
heating
Heating cycle rate 4
5
6
7
Cooling output
8
stages
Cooling cycle rate 9
10
11
System setting
12
adjustment
(models with
System key)
Not used
13
Degree
14
temperature
display
Displaying
15
temperature
(T7300F only).
Clock format.
16
Intelligent Fan™
17
operation.
Auxiliary contact
18
operation.
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
Table 7. Thermostat Installer Setup Options.
Factory Setting
Display
Description
0
Conventional applications where
equipment controls fan operation
in heat mode.
Subbase
Stages of heat.
dependant
4
Stage 1: 4 cph.
4
Stage 2: 4 cph.
4
Stage 3: 4 cph.
4
Emergency heat relay is on
continuously. Highest stage of
heat cycles at 4 cph (Q7300C or D
only).
Subbase
Stages of cooling.
dependant
4
Stage 1: 4 cph.
4
Stage 2: 4 cph.
4
Stage 3: 4 cph.
Model
System selection.
dependant
0
Temperature displayed in °F.
0
Temperature displayed.
0
12-hour clock format.
2
Fan operates continuously in
Occupied and recovery modes.
Fan operates with call for heat or
cool in Unoccupied mode.
0
0: Time of day contact.
11
IMPORTANT
Only configurable numbers are shown on the device.
Example: If the thermostat does not have a system
key, Installer Setup number 12 will not be displayed.
Review Table 7 factory settings and mark any
desired changes in the Actual Setting column. When
the Installer Setup is complete, review the settings to
confirm that they match the system.
Other Choices
(Press
Display
1
Electric heat applications where thermostat
controls fan operation in heat mode.
0, 1, 2,
0: No heating.
or 3
1: One stage of heat.
2: Two stages of heat.
3: Three stages of heat.
3, 6, 8 or
3: 3 cph (hot water systems or high
9
efficiency furnaces).
6: 6 cph (conventional systems).
8: 8 cph (conventional systems).
9: 9 cph (electric heat systems).
0, 1, 2 or
0: No cooling.
3
1: One cooling stage.
2: Two cooling stages.
3: Three cooling stages.
3
3: 3 cph.
0, 1 or 2 0: System setting key is operational.
1: Auto setting disabled.
2: Auto only setting.
1
Temperature displayed in °C.
1
Temperature not displayed.
1
24-hour clock format.
0 or 1
0: Fan operates only with call for heat or
cool (Occupied and Unoccupied modes).
1: Fan operates continuously in Occupied
mode. Fan operates with call for heat or
cool in Unoccupied mode.
1
1: Economizer contacts.
or
to change)
Actual
Description
Setting
63-4355—4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents