S9360, S9361, S9370, S9371 INTEGRATED BOILER CONTROLLERS
Connection
Line Voltage Input/White
Induced Draft Blower (Combustion Air
a
Vent Damper
/White
Spark Rod
a
On/Off Circulator
/Red
a
Indicates optional connections based on configuration.

Temperature Control

Temperature control setpoint on the module can be
adjusted as described in the following sections. Some
modules with temperature control also include a three-
digit display on the printed circuit board to facilitate
adjustments and troubleshooting.
For modules that do not include temperature control on
the module refer to the Honeywell Installation Instructions
for the specific interface module or the appliance
manufacturer's instructions. A separate automatic gas
shutoff device is not required in a system that uses this
control to meet requirements for CSA International ANSI
Z21.87 and UL 353.
The overall range of the setpoint is model-dependent but
is within 130°F to 240°F (54°C to 116°C). Select devices
may have different ranges.
69-2076—03
Table 5. Spark-to-Pilot Model Specific Connectors.
a
)/White
Table 6. Pin Configuration.
Line In
Transformer Primary
Transformer Secondary socket
Circulator
Damper
Inducer
Control
Sensor 1
Sensor 2
E-COM Diagnostic
Pin
1 of 4
Molex
2 of 4
3 of 4
4 of 4
1 of 6
Molex
2 of 6
3 of 6
4 of 6
5 of 6
6 of 6
1 of 6
2 of 6
3 of 6
4 of 6
5 of 6
6 of 6
1 of 1
1/4 in. female quick-
connect
1 of 2
Molex
2 of 2
Wire Harness Housing Pin Configuration
Pin/Socket
pin
socket
pin
pin
socket
socket
socket
socket
socket
Adjusting Settings for Models with
"On-Board" Display
To discourage unauthorized changing of settings, a
procedure to enter the adjustment mode is required. To
enter the adjustment mode, press the UP, DOWN, and I
buttons (see Fig. 1) simultaneously for three seconds.
Press and release the I button until the parameter
requiring adjustment is displayed:
"SP_"
Setpoint.
"Df_"
Setpoint Differential (select models).
"°F_"
Degrees Fahrenheit
"rSt"
Reset from Soft or Hard Lockout (select models)
Then press the UP or DOWN button until the parameter
has reached the desired value. After 60 seconds without
any button inputs, the control will automatically return to
the READ mode.
10
Mating Plug
L1
®
50-81-1040
Earth Ground
Earth Ground
Neutral
Earth Ground
®
39-01-2060
N/C
Neutral
N/C
L1 Relay Out
N/C
24 Vac
Damper E.S.
Feedback
24V Common if
damper connected
24V Common
Damper Activation
N/C
Connection to Spark
Rod
L1 Relay Out
®
50-84-1021
Neutral
®
Molex
Number
02-08-2004
02-08-1002
02-08-1002
02-08-2004
03-06-2103
39-00-0039
02-08-1002
08-50-0106
08-50-0106
08-50-0114
Description