Operation And Checkout; High Limit Controller - Honeywell S9360A Installation Instructions Manual

Integrated boiler controllers
Hide thumbs Also See for S9360A:
Table of Contents

Advertisement

S9360, S9361, S9370, S9371 INTEGRATED BOILER CONTROLLERS
1. Use tapping provided by tank manufacturer, if pos-
sible, or select an area where typical water temper-
ature is best measured.
2. If tank is filled, drain to below point where bulb will
be installed.
3. Screw well into tank.
4. Insert bulb into well, pushing wires until bulb bot-
toms in well.
5. Attach mounting clamp end of well spud.
6. With mounting clamp attached to well spud (make
sure jaws of clamp hook over ridge at end of spud,
as shown at points A in Fig. 8), adjust sensing lead-
wire to fit through mounting clamp groove, as
shown at point B in Fig. 8.
7. Tighten draw nut until mounting clamp is firmly
attached to well spud and wires are held securely in
place.
CAUTION
Do not secure draw nut so tightly that
mounting clamp collapses tubing.
SENSOR WIRES
Fig. 8. Immersion well fitting for sensor.
Wiring
Disconnect power supply before installation to prevent
electrical shock or equipment damage. All wiring must
comply with local codes and ordinances regarding wire
size, type of insulation, enclosure, etc.
69-2076—03
BOILER
IMMERSION
SENSOR
WELL
HEAT-CONDUCTIVE COMPOUND
(OPTIONAL)
M23086A

OPERATION AND CHECKOUT

Operation
The S9360A, S9361A, S9370A and S9371A continuously
monitor the temperature of the boiler water and enable or
disable the burner based on this temperature data. In
general, when a "Call for Heat" occurs, the ignition portion
of the control module proceeds through the steps
necessary to start the burner and heats the water in the
boiler until the setpoint temperature is achieved. At this
point the burner is de-activated, the ignition module
completes the heating cycle, returns to idle and waits for
the temperature to drop again. The circulator is turned on
throughout the "Call for Heat."
See Fig. 9 for a graphical representation of a simple
control cycle. Note that the setpoint differential may vary
based on OS number.

High Limit Controller

All models include a 3-wire temperature sensor interface,
"Sensor 1," which is utilized for High Limit functionality in
addition to the thermostatic control of the water heater
burner. If the temperature sensor ever indicates a
temperature above the maximum limit then the control
enters over temperature mode. In over temperature mode
no heating will occur.
200°F (93.3°C)
SETPOINT
15°F (8°C)
DIFFERENTIAL
70°F (21°C)
Fig. 9. Basic control algorithm example.
12