Properties
1.1 Power module PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
Technical data PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
Dimension B (mm)
Weight
Rated load voltage
•
Protection with automatic circuit breakers
Max. current-carrying capacity
•
•
•
Electrical isolation
•
•
Insulation test voltage
Current consumption from backplane bus
•
Power dissipation of the module
Parameter length
Diagnostic function
•
•
•
•
The fuses (order number: 6ES7193-4KA10-0AA0) for this module are only intended to serve as
1
supplementary fuses. External overcurrent protection (suitable for branch circuits in accordance with
the electrical engineering regulations that apply to your country) is required for the supply lines of the
load circuit.
10
Overvoltage protection
For 24 to 56.7 VDC
For 24 to 48/120/230 VAC
Short-circuit protection
Between rated load voltage and backplane
bus
Between the power modules
From load voltage L1/L+ (no load)
Group error
Load voltage monitoring
Fuse
Diagnostic information can be displayed
Dimensions and weight
15
34 g
Voltages, currents, potentials
24 VDC to 56.7 VDC
24 V to 48 V / 120 V / 230 V AC
Yes
Yes, tripping characteristic B, C
10 A
Up to 30°C: Max. 10 A
Up to 40°C: Max. 9 A
Up to 60°C: Max. 7 A
Up to 30°C: Max. 8 A
Up to 40°C: Max. 7 A
Up to 60°C: Max. 5 A
Yes, IEC 127-2/1, 250 V, 10 A,
fast fuse (5 x 20 mm), replaceable
Yes
Yes
1500 VAC
Max. 9.5 mA
Max. 9 mA
Max. 5 W
3 bytes
Status, interrupts, diagnostics
Yes
Red "SF" LED
Green "PWR" LED
Green LED "FSG"
Yes
Power module PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
1
Manual, 04/2007, A5E01120024-01