Error Types - Siemens Metro 21 M216KASPC  Operator's Manual

Distributed i/o power module pm-e
Table of Contents

Advertisement

Diagnostics

3.2 Error types

3.2
Error types
Power module error types
The diagnostic message is reported on channel 0 and applies to the entire module.
The table below shows the types of errors affecting power modules
Table 3-1
17
D
18
D
14
Power module error types
Error type
10001: Encoder or load
voltage missing
10010: Fuse is defective
Meaning
Supply voltage not present
or too low.
The fuse in the power
module has tripped.
Power module PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
Remedy
Correct the process wiring. Check
the supply voltage.
Replace the fuse.