Safety Precautions - Daikin Quaternity H-Series Engineeiring Data

H-series split-system room air conditioners
Table of Contents

Advertisement

Optional Accessories
13.2.2 KRP928B2S

Safety Precautions

Read these Safety Precautions carefully to ensure correct installation.
This manual classifies precautions into WARNING and CAUTION.
WARNING :
Failure to follow WARNING is very likely to result in such grave
consequences as death or serious injury.
CAUTION :
Failure to follow CAUTION may result in serious injury or
property damage, and in certain circumstances, may result in
a grave consequence.
Be sure to follow all the precautions below ; they are all important for
ensuring safety.
 Installation should be left to the dealer or another qualified professional.
Improper installation by yourself may cause malfunction, electrical shock, or fire.
 Install the set according to the instructions given in this manual.
Incomplete or improper installation may cause malfunction, electrical shock, or fire.
 Be sure to use the standard attachments or the genuine parts.
Use of other parts may cause malfunction, electrical shock, or fire.
 Disconnect power to the connected equipment before starting installation.
Failure to do so may cause malfunction, electrical shock, or fire.
 An earth leakage circuit breaker should be installed.
If the breaker is not installed, electrical shock may occur.
 Do not install the set in a location where there is danger of exposure to
inflammable gas.
Gas accumulated around the unit at the worst may cause fire.
 To prevent damage due to electrostatic discharge, touch your hand to a
nearby metal object (doorknob, aluminum sash, etc.) to discharge static
electricity from your body before touching this kit.
Static electricity can damage this kit.
 Lay this cable separately from other power cables to avoid external
electrical noises.
After installation is complete, test the operation of the PCB set to check
for problems, and explain how to use the set to the end-user.
<Wiring procedure>
Room air conditioner indoor unit
DAIKIN
To HA connector (S21)
Once the switches are set and
the wiring complete, secure the
case using the included
screws.
Cable available field supply
(See the installation manual of
the central remote controller)
Non polarity
Included in the Drain
Central controller equipment
 DCS302
Series
 DCS301
Series
 DCS601
Series
 DST301
Series
KRC65, KRC72,
KDC100A10, and KDC101B
Series cannot be connected.
In case that a central remote
controller is connected
76
WARNING
CAUTION
3.Names of Parts and Electric Wiring
Lower group number
switch (SW1)
Supplied connection harness
Separately sold remote control code (quadplex)
Up Kit.
KRCW101A Series
 Remote controller
Tele-con (Field supply)
BRC944
The adapter included with the
remote controller is not used.
In case that the device coping
Connecting a Wired
with HA JEM-A is connected
Remote Controller
1.Overview, Features and Compatible Models
This kit is the interface required when connecting the central controller and a Daikin Room Air
Conditioner. Use of the central controller makes it possible to perform the following monitoring
and operations. It is compatible with room air conditioners which have an HA connector S21.
1.Run / stop for the central controller and wired remote controller, operating mode
selection, and temperature can be set.
2.The operating status, any errors, and the content of those errors can be monitored
from the central controller and wired remote controller.
3.Run / stop for the central controller and wireless remote controller, operating mode
selection, and the temperature setting can be limited by the central controller.
4.Zone control can be performed from the central controller.
5.The unit can remember the operating status of the air conditioner before a power
outage and then start operating in the same status when the power comes back
on.
6.Card keys, operating control panels, and other constant / instantaneous
connection-compatible equipment can be connected.
7.The Operating / error signals can be read.
8.HA JEM-A-compatible equipment can be connected.
9.The indoor temperature can be monitored from the Ve-up controller.
Precaution
1.When reading the Operating / error signals, a separate external power source
(DC 12V) is needed.
2.A separate timer power source (DC 16V) is needed when using the schedule
timer independently, and not in conjunction with other central controllers.
3.The range of temperatures that can be set from the central controller is 18°C to
32°C in cooling and 14°C to 28°C in heating.
4.Fan operation cannot be selected from the central controller or wired remote controller.
5.Group control (i.e., control of multiple indoor units with a single remote controller) is
not available.
6.Monitoring is not available of the thermo status, compressor operating status,
indoor fan operating status, electric heater, or humidifier operating status.
7.Forced thermo off, filter sign display and reset, fan direction and speed settings,
air conditioning fee management, energy savings instructions, low-noise
instructions, and demand instructions cannot be made.
2.Component Parts and Separately-Sold Parts which are Required
This kit includes the following components. Check to ensure that none of
these are missing.
Parts
Kit assy
PCB is in the housing.
Screw cover
Upper group number
switch (SW2-1to 3)
Operation when recovering
from a power outage
mode
switch (SW2-4)
1
ON
1 2 3 4 1 2 3 4
0
OFF
SW1
SW2
S6
Tes1
S1
S8
S16
S19
F1
F2
 Card key
Series
(Field supply)
 Operating control panel
(Field supply)
Connecting a Momentary / constant
Contact Input Equipment
Q'ty
Parts
Connection harness (about 1.6m)
Mounting screws
1
Binding band
Installation manual
Service monitor (LED1: green)
When the CPU is working
properly, the LED flashes.
Japanese unit / Overseas unit
Setting switch (SW3-3)
Momentary contact / constant contact
Selection switch (SW3-2)
Forced stop
Settings switch (SW3-1)
LED1
Power supply terminal (S8)
SW3
Connect an external DC 12V power
supply only when reading the
S5
Operating / error display.
A cable field supply
A cable field supply
 Operating monitoring
equipment
(Field supply)
Reading the Operating / error Display
Room Air Conditioners H-Series
EDUS04-906_b
Q'ty
1set
3pcs.
1pc.
1set