Daikin Quaternity H-Series Engineeiring Data page 78

H-series split-system room air conditioners
Table of Contents

Advertisement

EDUS04-906_b
4.Switch Settings
T u rn the power on after all the switches have been set.
NOTE
Settings made while the power is on are invalid.
Open the Kit's case and set the switches on the circuit board.
(1) For Overseas / Japanese unit setting (SW3-3)
Room air conditioners, different methods are used for setting the temperature in
automatic mode, so this switch needs to be set.
Destination
SW3-3 setting
OFF
Japan
(Factory setting)
Overseas
ON
(2) Group number settings (SW1 and SW2-1 to SW2-3)
Set these when using the central controller. (Set to the
than one unit to the same number.
However, these settings do not need to be made when using the schedule timer
independently .
(The settings are needed when used in conjunction with another DCS Series
central controller.)
In this case, the schedule timer performs an auto address after the power is turned
on, so new group numbers are automatically set. Settings made using the switches
will be overwritten.
Upper
SW2
group NO.
setting
1
1 2 3
1—
0
1 2 3
2—
1 2 3
3—
1 2 3
4—
1 2 3
5—
1 2 3
6—
1 2 3
7—
1 2 3
8—
NOTE also that a separate timer power source is needed when using the
schedule timer independently.
Power source specs: DC 16V, +10%, -15%, 200mA.
Recommended power source: Omron S82J-01015A. (Should be used with the
output voltage adjusted to the center, DC 16V.)
(3) Settings when recovering from a power outage (SW2-4)
This selects whether to restart operation when the power comes back on after a
power outage occurred during operation. This setting is given priority in cases
where the indoor unit has an auto start ON / OFF jumper. Note also that
regardless of whether switch SW2-4 is on or off, the operating mode, set
temperature, fan direction and speed settings, and remote control prohibition
status are stored.
SW2-4 setting
OFF
Stops after recovering from a power outage
(Factory setting)
Stops if the unit was stopped before the power outage
ON
and runs if it was running.
(4) Contact input function settings (SW3-1 to SW3-2)
When using contact input (S1), choose one of the following functions.
S1
SW3-1
SW3-2
operating mode
setting
setting
Instantaneous contact
OFF
input (factory setting)
OFF
Constant contact input
ON
Forced stop or remote
ON
Invalid
controller permission input
NOTE1: Since central equipment and HA JEM-A-compatible equipment both use
last command priority, the contact status and operating status of the air
conditioner might not match sometimes.
Example: If the unit is run from the central controller while the air
conditioner is stopped with an open contact, the contact will be
open and the unit will be running.
NOTE2: Operating mode and fan direction and speed settings can be changed.
KRP928B2S
CA
S1
CB
Room Air Conditioners H-Series
What Happens
"Automatic" operation is not available from the central controller.
When using "automatic" operation using the wireless remote
controller, the central controller displays automatic cooling
(heating) and 77 °
F
(25°C). Even if the temperature is changed, it
will return to 77°F (25°C) after a while.
"Automatic" operation is available from the central controller.
side.) Do not set more
Lower
Lower
SW1
SW1
group NO.
group NO.
setting
setting
1
1 2 3
4
1 2 3
4
0 0
0 8
0
1 2 3
4
1 2 3
4
0 1
0 9
1 2 3
4
1 2 3
4
0 2
1 0
1 2 3
4
1 2 3
4
0 3
1 1
1 2 3
4
1 2 3
4
0 4
1 2
1 2 3
4
1 2 3
4
0 5
1 3
1 2 3
4
1 2 3
4
0 6
1 4
1 2 3
4
1 2 3
4
0 7
1 5
What Happens
What Happens
Control mode
The operating status of the air conditioner
is reversed by an instantaneous input of
Last command priority
100 msec or more.
Contact - Open to close: air condition runs.
ON / OFF control is rejected
Close to open: air conditioner is stopped
(operate / stop / timer prohibition)
(NOTE 1).
(NOTE 2).
During a forced stop, all
Contact - Open to close: air condition stops
remote controller actions
(forced stop). Close to open: no change in
are prohibited.
operating status.
Run / stop Input
Contact specs
No-voltage minute electric current contact
(Minimum applicable load DC 12V, 1mA or lower)
Total wire length max: 328 ft (100 m)
5.Control Codes
When using a central remote controller, the operating codes can be used to limit
operation from wireless remote controllers.
: permitted; ´ : prohibited
Operations from the remote controller
"Run" control from the
central controller
S1
Control
Control mode
operating
code
mode
´
´
0,1,3
ON / OFF control
´
´
is rejected
10,11
2
Only OFF control
´
is accepted
12–19
4
Instantaneous
Central priority
5
contact mode
Last command priority
6,7
Timer operation
*
*
8
is accepted by
*
*
9
remote controller
2,10-19
0,1,3,5-7
Constant
´
´
contact mode
4
8
9
´
´
Forced stop
*Only during timer operation
The remote controller permission / prohibition settings using the Ve-up controller are as
follows.
: permitted; ´ : prohibited
Ve-up controller settings
Operations from the remote controller
S1 pin
operating mode
Start / stop Change operating
Change set
temperature Run / timer
mode
Instantaneous
´
permitted
permitted/prohibited
ON / OFF
contact mode
control is
´
Constant
rejected
permitted/prohibited
prohibited
contact mode
´
permitted
Instantaneous
permitted
prohibited
´
contact mode
Only OFF
prohibited
permitted/prohibited
control is
´
permitted
accepted
Constant
permitted
prohibited
´
contact mode
prohibited
permitted/prohibited
permitted
Instantaneous
permitted/prohibited
´
contact mode Last command
prohibited
permitted/prohibited
´
permitted
Constant
priority
permitted/prohibited
´
contact mode
prohibited
permitted/prohibited
´
Forced stop
Does not affect settings
6.Read Operating / Error Display Signal
The Operating / error signals can be read from the contact output (S5).
Output specs
M1: T u rn MR 1 ON when the air conditioner is running.
M2: T u rn MR 2 when a communication error has occurred between the KRP928B2S and
the air conditioner, or MR 1 is ON and the unit has stopped after an error.
MR 2 is not turned ON during a warning.
KRP928B2S
S8
Power supply for relay (DC 12V)
Operating control panel (Field supply)
(+)
MC
MR1
(–)
S5
M1
MR1
Operating Display
MR2
(–)
Abnormality display
M2
MR2
7.Combining Equipment
The central controller can be combined with the following devices.
Central Remote Controller
ON / OFF controller
Schedule timer
D-BIPS
Forced stop contact input
Constant contact input
Instantaneous contact input
HA JEM-A-compatible equipment
Wired Remote Controller
Wireless Remote Controller
Optional Accessories
Operations from
"Stop" control from the
central controller,
central controller
contact input and
HA JEM-A input
´
´
´
´
´
´
´
´
´
´
´
´
´
´
´
*
´
´
*
´
´
´
´
´
´
*
*
´
´
´
´
´
´
Operations from
central controller,
contact input and
HA JEM-A input
Operating mode
Fan direction
Stop
temperature
and fan speed
´
´
´
´
´
´
´
´
´
´
´
´
´
´
´
Relay specs (MR1 and MR2)
Coil voltage: DC 12V
Coil resistance: 160W ± 10%
Power source
(Matsushita Electric HC
for display
Relay, Omron MY Relay )
Wiring length
Max: 328 ft (100 m)
´
´
´
´
´
´
´
´
´
´
´
´
´
´
´
´
´
3P157704-2B
77