Haier HSU-18,22HVA103/R2(DB) Service Manual page 86

V series wall mounted type
Table of Contents

Advertisement

(A)
Check the status of LED1 on
the indoor mainboard. If the
LED1 blinks interruptedly?
No
Test the outdoor power supply
(230VAC and +310VDC) with a
multimeter.
If
both
230VAC
310DC
available,measure
YES
If the LED1 is off within two minutes
after the machine is supplied with
power, measure the AC voltage between
positions 1 and 3 on the terminal of
outdoor unit with a multimeter.
If the value varies between 0 and 80
VAC, the outdoor mainboard is
damaged, replace it with a new one.
HSU-18,22HVA103/R2(DB)
If 230VAC is available but
310DC not, the power module is
damaged, replace it with a new
one.
and
NO
are
The outdoor mainboard is damaged;
Replace them with a new one.
Yes
measure the voltage between Jumpers
3 and 4 of IC15 on the indoor
mainboard with a multimeter.
If the voltage is of a
constant value of 0V
The indoor mainboard is
damaged; replace it with
a new one.
If the value is constant at about 30V,
the indoor mainboard is damaged,
replace it with a new one.
The outdoor mainboard is damaged;
replace it with a new one.
85
Service Diagnosis
NO
Yes
Domestic Air Conditioner