Westerbeke BTD 8.0 KW 60Hz Operator's Manual page 23

Diesel, single and three phase generators
Table of Contents

Advertisement

SYSTEM SPECIFICATIONS CONTINUED ...
General - 3 Phase
10.0 KW - 60 Hertz
7.5 KW - 50 Hertz
Voltage - 3 Phase (60 Hertz)
Voltage - 3 Phase (50 Hertz)
Amperage - 3 Phase (60 Hertz)
Amperage - 3 Phase (50 Hertz)
AC GENERATOR:
ENGINE COMBUSTION
AIR
REQUIREMENTS (60 Hertz) AT
1800 rpm
ENGINE COMPARTMENT COOLING
AIR
TUNE UPSPECIFICATIONS
INJECTOR PRESSURE
ENGINE TIMING
Brushless six pole, revolving field. Sealed lubricated
single bearing design. 12 Lead reconnectable for
low voltage WYE, high voltage Delta. Solid State
voltage regulator with protection circuitry.
Low voltage WYE
208 volts
High voltage WYE 480 volts
DELTA
240 volts
High voltage WYE 380 volts
DELTA
220 volts
Low voltage WYE
35 Amps
High voltage WYE
15 Amps
DELTA
30 Amps
High voltage WYE
14 Amps
DELTA
24 Amps
32 cfm (.906 cmm)
100-200 cfm (2.83 - 5.66 cmm)
1707 psi (120 kg/cm 2
+
10 kg/cm 2 - 0 kg/cm 2 )
19' BIDC
21
WESTERBEKE GENERATORS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents