3–26
"B" Group: Fine Tuning Functions
Func.
Name /
Code
SRW Display
B_12 Level of electronic
thermal setting
E-THM LVL 03.00A
B212 Level of electronic
thermal setting, 2nd
motor
2E-THMLVL 03.00A
B_13 Electronic thermal
characteristic
E-THM CHAR
B213 Electronic thermal
characteristic, 2nd
motor
2E-THMCHAR
WARNING: When parameter B_12, level of electronic thermal setting, is set to device
FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor
overload protection at 115% of device FLA or equivalent. Parameter B_12, level of
electronic thermal setting, is a variable parameter.
NOTE: For inverter models 005NFE, 011NFE, and 030HFE, the thermal value is less
than the rated amperes (is the same as models 004NFE, 007NFE, and 040HFE respec-
tively). Therefore, be sure to set the electronic thermal overload according to the actual
motor driven by the particular inverter.
"B" Function
Description
Set a level between 50% and
120% for the rated inverter
current.
Set a level between 50% and
120% for the rated inverter
current.
Select from two curves, option
codes:
00... Reduced torque
CRT
01... Constant torque
Select from two curves, option
codes:
00... Reduced torque
01... Constant torque
CRT
Defaults
Run
Mode
–FE
–FU
–FR
Edit
(CE)
(UL)
(Jpn)
Rated current for each
inverter model
*See note
Rated current for each
inverter model
*See note
01
01
01
01
Units
A
A
00
00