Hitachi SJ100 Instruction Manual page 94

Sj100 series
Hide thumbs Also See for SJ100:
Table of Contents

Advertisement

3–22
"A" Group: Standard Functions
Func.
Name /
Code
SRW Display
A_95 Acc1 to Acc2 frequency
transition point
ACC CHFr 000.0Hz
A295 Acc1 to Acc2 frequency
transition point, 2nd
motor
2ACCCHFr 000.0Hz
A_96 Dec1 to Dec2 frequency
transition point
DEC CHFr 000.0Hz
A296 Dec1 to Dec2 frequency
transition point, 2nd
motor
2DECCHFr 000.0Hz
NOTE: For A_95 and A_96 (and for 2nd motor settings), if you set a very rapid Acc1 or
Dec1 time (less than 1.0 second), the inverter may not be able to change rates to Acc2 or
Dec2 before reaching the target frequency. In that case, the inverter decreases the rate of
Acc1 or Dec1 in order to achieve the second ramp to the target frequency.
"A" Function
Description
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 360.0 Hz
Output frequency at which
Accel1 switches to Accel2,
range is 0.0 to 360.0 Hz
(2nd motor)
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 360.0 Hz
(2nd motor)
Defaults
Run
Mode
–FE
–FU
–FR
Edit
(CE)
(UL)
(Jpn)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
Units
0.0
Hz
0.0
Hz
0.0
Hz
0.0
Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents