Option
Terminal
Function Name
Code
Symbol
13
USP
Unattended Start
Protection
15
SFT
Software Lock
16
AT
Analog Input
Voltage/current
Select
18
RS
Reset Inverter
19
PTC
PTC Thermistor
Thermal Protection
27
UP
Remote Control
UP Function (motor-
ized speed pot.)
28
DWN
Remote Control
DOWN Function
(motorized speed
pot.)
Note 1:
When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F_01 or change the value of F_01 while the inverter is in Run Mode
(motor running). If it is necessary to check the value of F_01 during Run
Mode, please monitor D_01 instead of F_01.
Input Function Summary Table
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
ON
Terminal [OI] is enabled for current input (uses
terminal [L] for power supply return)
OFF
Terminal [O] is enabled for voltage input (uses
terminal [L] for power supply return)
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
ANLG When a thermistor is connected to terminals [5]
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
OPEN
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
ON
Accelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF
Output to motor operates normally
SJ100 Inverter
Description
3–37