Hitachi SJ100 Instruction Manual page 183

Sj100 series
Hide thumbs Also See for SJ100:
Table of Contents

Advertisement

6–14
Maintenance and Inspection
Inverter Output Voltage Measurement Techniques
Taking voltage measurements around drives equipment requires the right equipment and
a safe approach. You are working with high voltages and high-frequency switching
waveforms that are not pure sinusoids. Digital voltmeters will not usually produce
reliable readings for these waveforms. And, it is usually risky to connect high voltage
signals to oscilloscopes. The inverter output semiconductors have some leakage, and
no-load measurements produce misleading results. So, we highly recommend using the
following circuits to measure voltage for performing the equipment inspections.
Voltage measurement with load
L1/R
L2/S
L3/T
V Class
200V Class 600V 0.01A min. 300V range
400V Class 100V 0.1A min.
HIGH VOLTAGE: Be careful not to touch wiring or connector terminals when working
with the inverters and taking measurements. Be sure to place the measurement circuitry
components above in an insulated housing before using them.
U/T1
Inverter
V/T2
W/T3
220 kΩ
2W
+
Diode Bridge
Voltmeter
600V range
Voltage measurement without load
L1/R
Inverter
L2/S
L3/T
Additional resistor
V Class
200V Class 600V 0.01A min. 300V range
400V Class 100V 0.1A min.
U/T1
V/T2
W/T3
5 kΩ
30W
220 kΩ
2W
+
Diode Bridge
Voltmeter
600V range

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents