SAFETY PRECAUTIONS • Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. • The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the "...
Page 3
Warning If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite. Prohibit If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated. Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle.
1. OPERATING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 °F DB / 71 °F WB 115 °F DB Cooling Minimum 67 °F DB / 57 °F WB 0 °F DB Maximum 80 °F DB / 67 °F WB 75 °F DB / 65 °F WB Heating Minimum...
2-2. Major Component Specifications 2-2-1. Indoor Unit Indoor Unit (Body) CS-KE12NB41 Control PCB Part No. CB-CS-KE12NB4U Controls Microprocessor Control Circuit Fuse 250V 3A Type Turbo Q'ty ... Dia. and Length inch (mm) 1 ... D12-5/8 / L5-3/4 (D322/L147) Fan Motor...
Page 14
Indoor Unit (Body) CS-KE18NB4UW Control PCB Part No. CB-CS-KE18NB4U Controls Microprocessor Control Circuit Fuse 250V 3A Type Turbo Q'ty ... Dia. and Length inch (mm) 1 ... D12-5/8 / L5-3/4 (D322/L147) Fan Motor Type DC Motor Model ... Q'ty SIC-62FV-D866-2 ... 1 No.
5. PERFORMANCE DATA 5-1. Temperature Charts Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1 Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 115V) (1) Low pressure performance chart Lo Fan Hi Fan (0.9) (0.7) (0.5) (25)
Page 24
Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1 Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 115V) (1) High pressure performance chart (3.5) (3.0) (2.5) (2.0) (1.5) (-5) (10) (15) (20) (25) Outdoor inlet air DB temp. °F(°C)
Page 25
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V) (1) Low pressure performance chart Lo Fan Hi Fan (0.9) (0.7) (0.5) (25) (30) (35) (40) Outdoor inlet air DB temp. °F(°C) (2) Operating current performance chart Lo Fan Hi Fan...
Page 26
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 230V) (1) High pressure performance chart (3.5) (3.0) (2.5) (2.0) (1.5) (-5) (10) (15) (20) (25) Outdoor inlet air DB temp. °F(°C) (2) Operating current performance chart (-5) (10)
6. ELECTRICAL DATA 6-1. Electrical Characteristics Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1 Cooling Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor + Compressor Performance at 115V Single-phase 60Hz Rating conditions Running amp. 0.21 12.39 12.6 Power input...
Page 34
Indoor Unit CZ-KE18NB4U & CZ-18BT1U Outdoor Unit CU-KE18NKU (1) Voltage:230V < > Cooling 230V Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor + Compressor Performance at 230V Single-phase 60Hz Rating conditions Running amp. 0.15 8.15 Power input 1,838 1,860 Rating conditions: Indoor air temperature:...
7. MAINTENANCE T ab 7-1. Address Setting of the Remote Controller The address can be set in order to prevent interference between remote controllers when two indoor units are installed near each other. The address is normally set to "A." To set a different address, it is necessary to change the address on the Fig.
7-2. Disconnecting and Connecting Positive Connector for Outdoor Unit One of the two types of connectors illustrated at left is used. Their basic structure is the same for each. How to Disconnect Hold the resin connector cover, and pull the connector off. You cannot disconnect the connector by pulling the wire since it is locked inside.
7-3. Disassembly Procedure To avoid electrical shock hazard, be sure to disconnect power before WARNING attempting to disassemble the unit. When a footstool, etc. is used for disassembling the indoor unit, be careful not to fall down. If you fall down, you might be injured seriously. 7-3-1.
Page 41
7-3-3. Remove the ceiling panel. (1) Open the clamp (4 locations) and remove the 2 lead wires from the clamps. (Fig. 6) (2) Remove the 4 screws fixing the corner cover (at 3 locations) and indicator cover (at 1 location). (Fig. 6) (3) Press the center 1 of the cover and remove the cover with the section 2 pulled down.
Page 42
7-3-4. Remove the indoor air temperature sensor. (1) Disconnect the connector CN08 (ROOM 2P) in the control box and remove the indoor air temperature sensor. (Fig. 10) Indoor air temperature sensor CN08 Fig.10 7-3-5. Remove the power box and control box. (1) Remove a screw and remove the terminal cover.
Page 43
(4) Disconnect the connector CN07 (DP 2P) in the power box. (Fig. 13) Remove a screw and disconnect the ground cable. (Fig. 13) (5) Disconnect the connector CN03 (DCM 6P) in the power box. (Fig. 14) (6) Remove the 4 screws and remove the power box. (Fig. 14) (7) Disconnect the connectors CN06 (FS 3P) and CN09 (COIL-1 2P) in the control box.
Page 44
For the removal of the following components, perform any work after removing the indoor NOTE unit (main body) from the ceiling. Main body lower section Heat exchanger sensor Drain pump Float switch Turbo fan Fan motor Heat exchanger 1. Perform the work after draining the water to prevent the water leakage from the drain pan. Put a bucket, etc., under the drain cap and remove the drain cap to drain the water.
Page 45
7-3-7. Remove the heat exchanger sensor. (1) Remove the heat exchanger sensor from the sensor holder. (Fig. 19) Heat exchanger sensor Holder Fig.19 7-3-8. Remove the drain pump and float switch. (1) Remove the 2 screws (Fig. 20) (2) Loosen the clamp and disconnect the drain hose from the drain pump. (Fig. 20) (3) Remove the drain pump from the main body upper section.
Page 46
7-3-9. Remove the turbo fan and fan motor. (1) Remove a nut and remove the turbo fan. (Fig. 22) (2) Remove the 2 screws and 3 nuts, and remove the fan motor. (Fig. 23) Turbo fan Screw Fan motor Fig.22 Fig.23 7-3-10.
8. FUNCTIONS 8-1. Operation Functions Emergency operation SENSOR DRY Emergency operation is available when the remote During DRY operation, the system adjusts the room controller malfunctions, has been lost, or otherwise temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment.
HIGH POWER NIGHT SETBACK This function acts to raise the power but keeps the AC system in When NIGHT SETBACK operation is set, the temperature and the same operating mode. fan speed settings will be adjusted automatically to allow This function is set with the HIGH POWER button on the remote comfortable sleep.
8-2. Protective Functions Overload prevention during heating Cold-air prevention during heating During HEAT operation, the temperature of the indoor heat During heating, the fan speed is set to "LL" (very low) or stopped. exchanger is used to control the frequency and lessen the load As the temperature of the indoor heat exchanger rises, the fan on the compressor before the protective device is activated.
• When the cause of the increase in electrical current is rectified, the system will resume operation in the original mode. Heating operation <CS-KE12NB41> Outdoor fan ON Cooling Dry Heating 4-way valve ON Peak current cut-off trips 22.5...
9. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 9-1. Precautions before Performing Inspection or Repair After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate.
(1) Self-diagnostics Lamps INDOOR UNIT OPERATION button OPERATION lamp TIMER lamp HIGH POWER lamp REMOTE CONTROL receiver Since the indications cover various units, the corresponding parts listed below may not be present in some models..OFF ..BLINKING ..ON INDICATION ON INDOOR UNIT HIGH OPERATION...
(2) If the self-diagnostics function fails to operate • No indicators illuminate and the Check the indoor unit. indoor fan does not rotate. • Check the power voltage. Blown Is the fuse blown? Normal Replace the circuit board or the fuse. Replace the controller.
Page 54
(3) Serial Communication Error Identification Procedure If the lamps on the main body show the following conditions after the completion of self-diagnostics, a communication error between the indoor unit and outdoor unit might be considered. In such a case, identify the breakdown section by using the following procedure. NOTE Refer to "Method of Self-Diagnostics"...
Page 55
( Continued from the previous page A. ) ( Continued from the previous page B. ) Is the voltage of about DC22V to 24V given between the terminals 2 and 3 on the indoor unit terminal strip (Serial Communication Line) ? (Fig.
Page 56
(3-2) Condition: E12 Troubleshooting Serial Communication Outdoor Unit Power 1. Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF. 2. Disconnect the cable from the terminal 3 on the Outdoor Indoor Unit unit terminal strip.
* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the indoor unit controller (3 locations). Measurement location Normal value CS-KE12NB41 CS-KE18NB4UW (1) Vm-Gnd: Between pin 1 and pin 3 DC 130V to 195V DC 280V to 340V...
Page 58
9-4-2. Outdoor Fan Motor This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. Perform the trouble diagnosis by Test Run mode described on Installation Instructions. Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors.
9-5. Noise Malfunction and Electromagnetic Interference An inverter A/C operates using pulse signal control and high frequencies. Therefore, it is susceptible to the effects of external noise, and is likely to cause electromagnetic interference with nearby wireless devices. A noise filter is installed for ordinary use, preventing these problems. However, depending on the installation conditions, these effects may still occur.
10. CHECKING ELECTRICAL COMPONENTS 10-1. Measurement of Insulation Ground wire Resistance Clip The insulation is in good condition if the resistance exceeds 1M ohm. Probe 10-1-1. Power Supply Cord Insulation Clamp the grounding wire of power cord with the lead tester Fig.
10-2. Checking Continuity of Fuse Fuse on PCB Ass'y Remove the PCB Ass'y from the electrical component box. Then pull out the fuse from the PCB Ass'y. (Fig. 5) Check for continuity using a multimeter as shown in PCB Ass'y Fig.
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 11-1. Characteristics of New Refrigerant R410A 11-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22. 11-1-2.
11-2. Checklist before Servicing Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of extrusion) by using the flare spacer.
11-3. Tools Specifically for R410A For servicing, use the following tools for R410A Tool Distinction Tool Name Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) Tools specifically for R410A (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached.
11-5. In Case of Compressor Malfunction Should the compressor malfunction, be sure to make the switch to a replacement CAUTION compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "11-3. Tools Specifically for R410A." 11-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the...
Page 66
Configuration and characteristics of cylinders (5) Recharging Valve Be sure to charge the specified amount of refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.
11-6. In Case Refrigerant is Leaking Never attempt to charge additional refrigerant when refrigerant has been leaking CAUTION from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points.
11-7. Charging Additional Refrigerant 11-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. Never charge additional refrigerant if refrigerant is leaking from the unit. Follow CAUTION instructions given in "11-6.
Operating Instructions Split System Air Conditioner Model No. Indoor Units Outdoor Units (For Single use) CS-KE12NB41 CU-KE12NK1 CS-KE18NB4UW CU-KE18NKU (For Multiple use) CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU Ceiling Panel CZ-18BT1U This air conditioner uses the refrigerant R410A. “Multiple use” is applied for the model CS-KE18NB4UW only.
FEATURES This air conditioner is an inverter type unit that automatically adjusts capability as appropriate. Details on these functions are provided below; refer to these descriptions when using the air conditioner. • Microprocessor Controlled Operation • Automatic Switching between Cooling and Heating The interior compartment of the remote controller contains When the remote controller’s S/M switch is at the “S”...
INSTALLATION LOCATION • To prevent possible hazards from insulation failure, the unit must be grounded. • We recommend that this air conditioner be installed • Do not clean inside the indoor and outdoor units by users. properly by qualified installation technicians in Engage authorized dealer or specialist for cleaning.
NAMES OF PARTS UNIT DISPLAY AND OPERATION BUTTON INDOOR UNIT INDOOR UNIT Air Intakes OPERATION button OPERATION lamp Air Outlet TIMER lamp (4 locations) HIGH POWER lamp REMOTE CONTROL receiver Remote Controller IMPORTANT Refrigerant Tubes Avoid using radio equipment such as mobile phone near (within OUTDOOR UNIT 4 ft.
Page 75
REMOTE CONTROLLER (DISPLAY) Displayed when transmitting data Displayed when indoor unit sensor is in use Displayed when setting temperature Displayed when temperature is shown Displayed when setting timer Displayed when the time display is set to 12-hour time. Symbols (1) Operation mode (4) Timer AUTO ........
Page 76
REMOTE CONTROLLER Transmitter When you press the buttons on the remote controller, the mark appears in the display to transmit the setting changes to the receiver in the air conditioner. Display Information on the operating conditions is displayed while the remote controller is switched on.
Page 77
Sensor A temperature sensor inside the remote controller senses the room temperature. ON/OFF operation button This button is for turning the air conditioner on and off. 1 HR. TIMER button (1-HOUR OFF TIMER) : When you press this button, regardless of whether the unit is operating or stopping, the unit operates for one hour and then shuts down.
USING THE REMOTE CONTROLLER HOW TO INSTALL BATTERIES HOW TO USE THE REMOTE CONTROLLER When using the remote controller, always point the unit’s transmitter head directly at the air conditioner’s receiver. Air Conditioner (Indoor unit) Receiver ACL button Slide the cover in the direction indicated by the arrow and remove (Transmitter Remote Controller head)
OPERATION WITH THE REMOTE CONTROLLER 1. Automatic Operation 2. Manual Operation When the remote controller’s S/M switch is at the “S” (Single) position This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting.
3. Adjusting the Fan Speed A. In Cooling and DRY Mode: ( A. Automatic fan speed When the night setback mode is selected, the air conditioner Simply set the FAN SPEED selector button to the automatically raises the temperature setting 2 °F when 30 minutes have passed after the selection was made, and then another 2 °F position.
SETTING THE TIMER • When the HIGH POWER button is pressed, the unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is 1 step above “High”. • HIGH POWER Mode cannot be used when the operation mode is in Automatic Operation.
Page 82
2. How to set the OFF time 4. How to set daily ON/OFF repeat timer (Example) To stop the air conditioner at 11:00 am. (Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am. 10:30 pm. 7:10 am.
USING THE 1-HOUR OFF ADJUSTING THE AIRFLOW TIMER DIRECTION The vertical airflow can be adjusted by moving the flap with the 1. 1-Hour OFF Timer remote controller. Do not move the flap with your hands. Confirm that the remote controller has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.
OPERATION WITHOUT THE CARE AND CLEANING REMOTE CONTROLLER • Cleaning and maintenance operations must be carried out by specially INDOOR UNIT trained personnel. While working in high places, slipping or falling may result in serious injury. • For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning.
Page 85
Air filter How to remove the air intake grille The air filter collects dust and other particles from the air and should Open the air intake grille. be cleaned once every 6 months. Detach the safety cord from the frame (remember to attach it If the filter gets blocked, the efficiency of the air conditioner drops again after cleaning or maintenance).
TROUBLESHOOTING OPERATING RANGE (BEFORE CALLING FOR SERVICE) The air conditioner is operable within the temperature ranges as listed below: If your air conditioner does not work properly, first check the following Temperature Indoor air Outdoor air points before requesting service. If it still does not work properly, temperature temperature contact your dealer or service center.
Page 87
SPECIFICATIONS • For Single use Outdoor Unit Indoor Unit Model No. CU-KE12NK1 CS-KE12NB41 Power Source Single-phase, 115 V, 60 Hz 3.50 [ 0.90 ~ 3.50 ] Cooling Capacity 11,900 [ 3,000 ~ 11,900 ] BTU/h 4.00 [ 0.90 ~ 4.00 ]...
Page 88
SPECIFICATIONS (CONTINUED) • For Multiple use Indoor Unit Model No. CS-KE18NB4UW Power Source Single-phase, 208-230 V, 60 Hz 5.15 Cooling Capacity 17,500 BTU/h 6.00 Heating Capacity 20,400 BTU/h Cooling Operation dB(A) 44/40/36 Operation (H/M/L) Sound Heating Operation dB(A) 44/40/36 (H/M/L) 11-5/32×22-5/8×22-5/8 Unit Dimensions (H×W×D) inch(mm)
1-3. Optional Copper Tubing Kit Model No. 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation Indoor Unit Outdoor Unit CS-KE12NB41 CU-KE12NK1 INSTALLATION SITE SELECTION ....5 2-1. Indoor Unit Power Source: 2-2. Outdoor Unit...
IMPORTANT! When Transporting Please Read Before Starting Be careful when picking up and moving the indoor and out- door units. Get a partner to help, and bend your knees when This air conditioning system meets strict safety and operating lifting to reduce strain on your back. Sharp edges or thin alu- standards.
Page 93
Others the flare and union tubes before connecting them, CAUTION then tighten the nut with a torque wrench for a leak- free connection. the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously or re-installation, and while repairing refrigeration parts. toxic gas.
Page 94
Narrow Tube Wide Tube and regulations before Model Outer Dia. Thickness Outer Dia. Thickness obtaining wire. Also, check CS-KE12NB41 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm) any specified instructions or limitations. CS-KE18NB4UW 1/4" (6.35 mm) 0.0314"...
Additional Refrigerant (ft.) (ft.) (ft.) (oz./ft.)* CS-KE12NB41 0.16 CS-KE18NB4UW 0.27 * If total tubing length becomes 25 to 65 ft. (Max.) or 25 to 100 ft. (Max.), charge additional refrigerant (R410A) by 0.16 or 0.27 oz./ft. No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
Page 96
2-2. Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc. (Fig. 3) Heat source damp, humid or uneven locations. Outdoor unit choose a place as cool as possible. choose a place that is well ventilated. Fig. 3 install in a location where at least two sides are unob- structed, so that the flow of air at the intake port or exhaust port is not blocked, and so that sufficient...
3. How to Install the Indoor Unit Hole-in-anchor Concrete Insert Hole-in-plug 3-1. Preparation for Suspending This unit uses a drain pump. Use a carpenter’s level to check that the unit is level. 3-2. Suspending the Indoor Unit Suspension bolt (M10 or 3/8") (1) Fix the suspension bolts securely in the ceiling using (locally purchased) the method shown in the diagrams, by attaching...
Page 98
Twist tie 3-4. Installing the Drain Piping (4 vinyl ties, supplied) Hard PVC pipe Drain hose (1) Prepare standard hard PVC pipe (locally purchased O.D. Position to Drain port (equivalent to insulation O.D. 1-1/32" (26mm)) fasten hose 1-1/32" (26 mm)) for the drain and use the supplied hose (supplied) bands (locally purchased)
Page 99
3-5. Checking the Drainage Water drain After wiring and drain piping are completed, use the following pro- cedure to check that the water will drain smoothly. For this, pre- pare a bucket and wiping cloth to catch and wipe up spilled water. Be sure to do the wiring between the units before installing the ceiling panel.
Page 100
(2) Removing the corner cover and indicator cover a) While lightly pressing the cen- ter of the corner cover, pull up the tab for the screw hole. Use the same procedure to Corner cover Press remove the indicator cover. (Fig. 6-16) Pull up Indicator cover Fig.
Page 101
3-6-3. Wiring the Ceiling Panel and the Indicator Drain pipe side (1) Remove the 2 screws from the control box cover, then open the cover. Be careful that the cover does not fall. (2) Connect the 5P FLAP wiring connector from the ceiling Control box panel to the connector on the control PCB in the control box.
Page 102
3-6-5. Checking After Installation Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling sur- face. Gaps may cause water leakage and condensation. Check that the wiring is securely connected. If it is not securely connected, the auto flap will not operate.
Page 103
Table 4 Cross-Sectional (A)+(B) (A) Power Supply Wiring Length (ft) (C) Control Fuse or Circuit Area (AWG) (B) Power Line Length (ft) Line Length (ft) Breaker Capacity Model (#14) (#12) (#14) CU-KE12NK1 131 (Max.) 230 (Max.) 65 (Max.) CU-KE18NKU 131 (Max.) 230 (Max.) 100 (Max.) # ...
Page 104
3-9. Wiring Instructions for Inter-unit Connections (1) Remove the 1 screw from the terminal cover, then open the cover. Be careful that the cover does not fall. (2) Remove the 3 screws from the power box cover, then open the cover. Be careful that the cover does not fall. (3) Use the screw to securely fasten the ground wire from the outdoor unit in place.
For stranded wiring (1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8" (10 mm) and tightly twist the wire ends. (Figs. 11 and 12) (2) Using a screwdriver, remove the terminal screw(s) on the terminal plate. (3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector.
5. Refrigerant Tubing Deburring Before After 5-1. Use of the Flaring Method Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
5-4. Connecting Tubing between Indoor and Torque wrench Outdoor Units a) Tightly connect the indoor side refrigerant tubing exten- Spanner Indoor unit ded from the wall with the outdoor side tubing. (Fig. 21) b) To fasten the flare nuts, apply specified torque as: Outdoor unit Table 5 Fig.
5-6. Taping the Tubes (1) At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing. (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall.
Page 109
(4) With the “Lo” knob of the manifold valve open, run NOTE the vacuum pump. The operation time for the vacu- um pump varies with tubing length and the capacity To prevent other refrigerants from being mistakenly of the pump. The following table shows the amount charged to units which use R410A, the size of the of time for evacuation: charge port on the service valve is different from the...
Page 110
How to Test Run the Air Conditioner After turning on the power of the air conditioner, use the remote controller and follow the steps below to conduct the test run. (1) Set the remote controller in Test Run mode. (Fig. 29) a)Press and hold the HIGH POWER button and the 1HR.
Basic Functions of the Service Valves The basic functions of the service valves are given in Table 7 below. Table 7 Narrow Tube Service Wide Tube Service Action Valve (2-Way) Valve (3-Way) O-ring Valve cap CLOSED Stem Shipping Fully OPEN Operating and test running the air conditioner...
Service Valve Connections a) Temporary connection: Screw in 3 – 5 turns by hand. (Fig. 34) b) To fasten the flare nuts, apply specified torque as Table 8 and Fig. 35. Table 8 Fig. 34 Tube Dia. Tightening Torque 1/4" (6.35 mm) 21/32"...
Page 113
8. Address Switch 8-1. Address Setting of the Remote Controller The address can be set in order to prevent interfer- ence between remote controllers when 2 indoor units are installed near each other. The address is normally set to “A.” To set a different address, it is necessary to change the address on the second remote controller.
Page 114
APPENDIX C Operating Instructions CZ-RD515U (852-6-4181-230-00-1)
“COOL/DRY Model” indoor unit. Once the wired remote controller is connected, the wireless remote controller cannot be used. Before operating the unit, read these operating instructions thoroughly and keep them for future reference. Panasonic Corporation 1006 Kadoma, Kadoma City, Osaka, Japan 85264181230001 CV6233187877...
FEATURES • Microprocessor Controlled Operation • Air Sweep Control The interior compartment of the remote controller contains several This function moves a flap up and down in the air outlet, directing features to facilitate automatic operation, easy logically displayed air in a sweeping motion around the room and providing comfort in for easy use.
INSTALLATION LOCATION • To prevent possible hazards from insulation failure, the unit must be grounded. We recommend that this wired remote controller be • Do not clean inside the indoor and outdoor units by users. installed properly by qualified installation technicians Engage authorized dealer or specialist for cleaning.
REMOTE CONTROLLER NOTE The descriptions on the AUTO ( ) or HEAT ( ) operation mode are only for the “COOL/DRY/HEAT Model,” and not for the “COOL/DRY Model.” Display Information on the operating conditions is displayed while the remote controller is switched on. If the unit is turned off, only the mode that was set previously is still displayed.
Page 119
ON/OFF operation button This button is for turning the air conditioner on and off. MODE selector button Use this button to select AUTO, HEAT, DRY, COOL or FAN mode. (AUTO) : When this setting is selected, the air conditioner calculates the difference between the thermostat setting and the room temperature and automatically switches to the ‘‘COOL’’...
Page 120
REMOTE CONTROLLER (DISPLAY) Displayed when indoor unit sensor Displayed when operating NIGHT is in use SETBACK mode Displayed when setting temperature Displayed when temperature is shown Displayed when setting timer Symbols (1) Operation mode (3) Temperature setting 60 – 86 °F ......AUTO ........
OPERATION WITH THE REMOTE CONTROLLER 1. Automatic Operation 2. Manual Operation (only for COOL/DRY/HEAT Model) • Single use This unit automatically switches between cooling operation and heating operation according to the difference between the room temperature and the temperature setting. •...
3. Adjusting the Fan Speed A. In Cooling and DRY Mode: ( A. Automatic fan speed When the night setback mode is selected, the air conditioner Simply set the FAN SPEED selector button to the automatically raises the temperature setting 2 °F when 30 minutes have passed after the selection was made, and then another 2 °F position.
SETTING THE TIMER 3. How to set the ON time (Example) To start operation at 7:10 am. ON TIME Present time Operation Indication Press the SET button once. The timer indication alone flashes and the previous set- time is only displayed. •...
USING THE 1-HOUR OFF ADJUSTING THE AIRFLOW TIMER DIRECTION The vertical airflow can be adjusted by moving the flap with the 1. 1-Hour OFF Timer remote controller. Do not move the flap with your hands. Confirm that the remote controller has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.
APPENDIX D INSTALLATION INSTRUCTIONS CZ-RD515U (852-6-4190-592-00-0)
Page 127
INSTALLATION INSTRUCTIONS Wired Remote Controller In order to install this wired remote controller onto a wall-mounted model, the connection kit IMPORTANT (CZ-RC515U or CZ-RC515UA), which must be purchased separately, is required. Once the wired remote controller is connected, the wireless remote controller cannot be used. Table 1 Parts supplied with the remote controller Parts...
Page 128
A. Installing with in-wall junction box In-wall junction box (locally purchased) (1) Install the junction box (locally purchased) into the wall. (Figs. 2-a and 3) (2) Pass the wire harness through the junction box and conduit. (Fig. 3) (3) Insert a flathead screwdriver into the 5 tab locations and disconnect the back plate of the remote controller by 2-3/8"...
Page 129
How to wire the remote controller 5P FLAP 7P IND and 4P RC Ceiling wiring connector wiring connector panel (1) Turn OFF the power and remove the ceiling panel air-intake grille. (Refer to 3-6-1 Before Installing the Ceiling Panel in the Installation Instructions supplied with the indoor unit.) (2) Remove the 3 power box cover screws and 2 control box cover screws, then remove both covers.
Page 130
How to Test Run the Air Conditioner After turning on the power of the air conditioner, use the remote controller and follow the steps below to conduct the test run. (1) Set the remote controller in Test Run mode. (Fig. 9) a)Press and hold the NIGHT SETBACK button and ON/OFF the 1HR.