Finishing

A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materi-
als (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
All measurements are in inches.
7
6
5
4
3
4
TOP OF HOOD OR FIREPLACE OPENING
Figure 13.1 Clearances to Mantels or other Combustibles
above Appliance
3-1/2 in.
1/2 in.
NON-COMBUSTIBLE ZONE
Figure 13.2 Non-Combustible Zone
Models: SL-550TR-E, SL-750TR-E
SL-550TR-IPI-E, SL-750TR-IPI-E
CEILING
12
11
10
9
8
32
13
12
11
10
9
8
7
6
5
1/2 in. SHEETROCK
OR COMBUSTIBLE
MATERIAL
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. L • 11/08
2-7/8 IN.
MINIMUM
Note: Clearance from opening
to perpendicular wall.
Figure 13.3 Mantel Leg (Acceptable on both sides of opening.)
5-3/8 IN.
MINIMUM
Note: Clearance from opening
to perpendicular wall.
Figure 13.4 Wall Projection (Acceptable on one side of opening.)
3-1/2 in.
1/2 in.
NON-COMBUSTIBLE ZONE
Figure 13.5 Non-Combustible Zone
Models: SL-950TR-E, SL-950TR-IPI-E
1/2 IN.
MINIMUM
3 FT. MAXIMUM
3 IN.
MINIMUM
UNLIMITED
1/2 in.
SHEETROCK
NON-COMBUSTIBLE
BOARD SHIPPED
WITH APPLIANCE
57