FLUE TERMINAL LOCATION

The flue design, installation and termination point must comply with NZS 5261. As a guide the following
requirements extracted from the New Zealand Gas Installations Standard NZS 5261, must be observed for
the flue termination.

Horizontal Flue Terminal Location

At least 300 mm between the top of the flue terminal and the eaves.
At least 300 mm between the bottom of the flue terminal and the ground, balcony or other surface.
At least 500 mm between the flue terminal and the edge of any opening into the building, measured
horizontally along the wall.
At least 300 mm between the flue terminal and a return wall or external corner, measured horizontally
along the wall.
At least 1500 mm between the top of the flue terminal and below any openable window measured
vertically.
At least 1500 mm between the flue terminal and any opening into a building, in the direction of the flue
discharge.
At least 500 mm between the flue terminal and a fence, wall or other obstruction, in the direction of the
flue discharge.
At least 300 mm between the flue terminal and any other flue terminal, cowl or other combustion air
intake.
For a multiple unit installation, refer to
between flue terminals.

Vertical Flue Terminal Location

At least 500 mm between the underside of the flue terminal and the nearest part of a non-trafficable roof.
At least 2000 mm between the underside of the flue terminal and the nearest part of a trafficable roof
designed for personal or public use.
At least 200 mm between the flue terminal and a chimney where the flue terminates above the chimney.
At least 500 mm between the flue terminal and the edge of any opening into the building, measured
horizontally.
At least 300 mm between the flue terminal and any other flue terminal, cowl or other combustion air
intake.
For a multiple unit installation, refer to
between flue terminals.
"Horizontal Flue Terminations"
"Vertical Flue Terminations"
59
on page 72 for minimum distances
on page 72 for minimum distances