Step 4. Positioning, Leveling, and
Securing the Fireplace
The diagram below shows how to properly position, level,
and secure the fireplace.
WARNING:
To ensure proper
clearances the
front framing
header must be
installed on its
narrow edge and
to the front of
the frame.
NAILING TABS
(BOTH SIDES)
Figure 28. Proper Positioning, Leveling, and
Securing of a Fireplace
• Place the fireplace into position.
• Level the fireplace from side to side and from front to
back.
• Shim the fireplace with non-combustible material, such
as sheet metal, as necessary.
• Secure the fireplace to the framing by nailing or screwing.
Hearth & Home Technologies • BE-36-C, BE-36-CIPI • 397-981 Rev. R • 2/05
Step 5. The Gas Control System
WARNING: THIS UNIT IS NOT FOR USE WITH
!
SOLID FUEL.
The gas control system used with model BE-36-C is
Standing Pilot Ignition.
Standing Pilot Ignition System
This system includes millivolt control valve, standing pilot,
thermopile/thermocouple flame sensor, and piezo ignitor.
WARNING: 110-120 VAC MUST NEVER BE
!
CONNECTED TO A CONTROL VALVE IN A
MILLIVOLT SYSTEM.
STANDING PILOT and IPI
Figure 29. Gas Control System
The gas control system used with model BE-36-CIPI is
Intermittent Pilot Ignition (IPI).
Intermittent Pilot Ignition (IPI) System
This system includes a 3V control valve, electronic module
and intermittent pilot.
WARNING: 110-120 VAC SERVICE MUST BE
!
WIRED TO THE FIREPLACE JUNCTION BOX.
3/8" (10mm)
29