Vent Information and Diagrams

A. Vent Guidelines
WARNING!
Fire Risk/Asphyxiation! This appliance requires
the specifi ed pipe for operation. Incorrect pipe may cause spill-
age, condensation and overheating.
These models require the following size B-vent double
wall, or single wall rigid or fl ex vent pipe.
Models
8000TV-OAK
• Follow pipe manufacturer's installation guidelines when
installing the appliance.
WARNING!
Fire Risk/Explosion/Asphyxiation!
connect this gas appliance to a chimney fl ue serving a
separate solid-fuel or gas burning appliance.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
May impair safe operation of this appliance or other appli-
ances connected to the fl ue.
B. Vent System Confi guration
CAUTION! Risk of Fire! ALL vent confi guration specifi -
cations MUST be followed.
to these specifi cations. Appliance performance will suffer if
specifi cations are not followed.
Rise to Run Ratio = 2:1
Maximum Total Horizontal Run = 15 Feet
Minimum Total Vertical Rise = 9 Feet
Maximum Total Vertical Rise = 30 Feet
Maximum Number of Elbows: Two 90º or Four 45º
Note: A rise of 1/4 inch per foot of horizontal run is required.
WARNING! Risk of Fire or Explosion!
er combustibles must not infringe on clearances.
• ALWAYS maintain specifi ed clearances around venting and
fi restop systems.
• Install fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe
may cause fi re.
Heat & Glo • 8000TV-OAK, 8000TV-OAK-IPI, 8000TVLP-OAKIPI • 2058-900 Rev. N • 11/08
Pipe Size
6 inch
DO NOT
This product is tested and listed
Insulation and oth-
Note: Other vent
components are
noted in Figure 4.2
9 FEET
MINIMUM
Figure 7.1
Note: Other vent
components are
noted in Figure 4.2
VENT SUPPORTS
ARE PER VENT
MANUFACTURER'S
SPECIFICATIONS.
MAXIMUM HORIZONTAL RUN IS 50%
OF VERTICAL. HORIZONTAL RUN
CANNOT BE MORE THAN 15 FT .
Figure 7.2
MINIMUM
VERTICAL
9 FEET
45 DEGREES
ELBOW
90 DEGREES
ELBOW
Figure 7.3
MINIMUM CLEARANCES
ARE PER VENT
MANUFACTURER'S
SPECIFICATIONS
METAL
PLUMBER'S
STRAP
VENT SUPPORTS ARE PER
VENT MANUFACTURER'S
SPECIFICATIONS
METAL
PLUMBERS' STRAP
Note: Horizontal runs require
1/4 in. rise per foot run.
MAXIMUM
HORIZONTAL
15 FEET
OFFSETS EXCEEDING
45 DEGREES ADAPT
HORIZONTAL LIMITATIONS
Note: Maximum horizontal
distance is 50% vertical vent
height or up to 15 feet.