Honeywell W180 User Manual page 37

Zone control system
Hide thumbs Also See for W180:
Table of Contents

Advertisement

2. Wire the sensor as shown in the job drawings and
Figs. 40 through 42.
3. Mount the space sensor circuit board on the mount-
ing plate (Fig. 43).
4. Mount the cover on the mounting plate (Fig. 44).
Fig. 40—T7660A Space Temperature Sensor
terminal connections.
LED LIGHT
LED
TEMPERATURE
T
SENSOR
ANALOG;
A
COMMON
JUMPER W1
Fig. 42—Typical T7660B Space Temperature Sensor wiring.
RTD SENSOR WIRES
T7660B SENSOR
PUSHBUTTON
PB
DIGITAL;
D
COMMON
W1
M8162
T
A
D
LED
PB
22 AWG
Fig. 41—Typical T7660A Space Temperature
Sensor wiring.
CABLE SHIELD
(IF REQUIRED)
T
T7660A SENSOR
A
18-22 AWG
TWISTED PAIR
HONEYWELL T7660A SENSOR
MAXIMUM DISTANCE FROM CONTROLLER
IS 300 FT. [91 M] USING 18 AWG
THERMOSTAT WIRE.
SENSOR GND
R2
2.2K,
1/4 WATT
SENSOR/INPUT
CONNECTIONS
–1
R1
+1
220
,
–2
1/8 WATT
+2
–3
+3
–4
+4
–5
+5
–6
+6
–7
+7
–8
+8
37
W180 ZONE CONTROL SYSTEM
SENSOR GND
SENSOR/INPUT
CONNECTIONS
M8174
SENSOR PWR
20 VDC
5 VDC
RELAY
CONNECTIONS
RLY 1
1/2 com
RLY 2
spare A
RLY 3
3/4 com
RLY 4
spare B
spare C
RLY 5
5/6 com
RLY 6
spare D
RLY 7
7/8 com
RLY 8
M8175
68-0139
–1
+1
–2
+2
–3
+3
–4
+4
–5
+5
–6
+6
–7
+7
–8
+8

Advertisement

Table of Contents
loading