W180 ZONE CONTROL SYSTEM
Fig. 51—Automatic opposed blade damper-bottom mount installation.
3 IN. [76mm]
DUCT
OPENING
NOTES:
1. Use the W180M software to easily monitor the sys-
tem status.
2. See the W180 Zone Control System Owner's Manual,
form 69-0770, for operating information on the
S321A Touchpad.
3. See Appendix A: Troubleshooting section for
troubleshooting information.
Before operating the system, perform the following
checks and tests:
1. Verify that all wiring is securely connected to the
correct terminals.
2. Verify that the temperature displayed on the Touchpad
for each sensor is within range and reasonable for the site
conditions.
3. Verify that the humidity reading displayed on the
Touchpad for the humidity sensor is within range and
reasonable for the site condition.
4. Verify that each alternate fuel device operates within
the specifications stated in the literature for the device.
5. Verify that each piece of HVAC equipment operates
properly as follows:
a. Dampers and fans:
1) Disable the heating/cooling equipment and man-
ually turn On the fans. Verify fan operation.
68-0139
2
1

Checkout and Test

2) Set the System Mode to Auto and use the
override function to change the setpoint in
each zone, one at a time.
a) Verify that the damper opens and closes
b) If using a PC on site, use the W180M Soft-
3) Enable the heating/cooling equipment from
step 1) and verify that the equipment operates
according to the setpoints set at each Touchpad.
4) Verify operation at each of the Auto/Heat/
Cool settings. Use the override function to
create a demand, if necessary.
b. Hydronic valves:
1) Use the override function to change a setpoint
in each zone, one at a time.
a) Verify that the circulation pump turns On
b) If using a PC on site, use the W180M Soft-
42
1
USE 1/4 IN. [6 mm] SHEET METAL
SCREWS PROVIDED.
2
FOR LONGER AIR DUCTS, SECURE
REAR OF DUCT USING TWO SHEET
METAL SCREWS PROVIDED.
appropriately.
ware at the PC to check that dampers are
positioned as shown on the monitor screen.
Dampers may also be positioned manually
to assist in system checkout.
and that the temperature in that zone
changes.
ware at the PC to check that the valve is
open or closed.
M2276B