Download Print this page

Specifications - Honeywell L91A Product Data

Proportioning pressuretrol controllers

Advertisement

L91A,B,D PROPORTIONING PRESSURETROL

SPECIFICATIONS

Operating Ranges
U. S.
Customary
Model
Units
L91A
0 to 15 psi
0 to 103 kPa
5 to 150 psi
0.03 to 1.03 MPa 23176CB
0.07 to 2.07 MPa 23176CB
b
10 to 300 psi
L91B
0 to 15 psi
0 to 103 kPa
0.03 to 1.03 MPa 23176CB
c
5 to 150 psi
0.07 to 2.07 MPa 23176CB
c
10 to 300 psi
10 to 300 psi
0.07 to 2.07 MPa 23176CF
L91D 0 to 15 psi
0 to 103 kPa
c
0.03 to 1.03 MPa 23176CF
5 to 150 psi
0.07 to 2.07 MPa 23176CF
c
10 to 300 psi
Models (Table 1):
L91A: Single potentiometer; nonadjustable proportioning
range.
L91B: Single potentiometer; adjustable proportioning range.
L91D: Two potentiometers allow unison control of motors;
adjustable proportioning range.
Electrical Rating: 24 Vac.
Potentiometer Action: Wiper moves toward W on pressure
rise, toward B on pressure fall. Potentiometer is field
replaceable.
Potentiometer Resistance: 140 ohms (nominal) for L91A, B,
and D models.
Pressure Sensing Element: Brass bellows, 10-300 psi
models phos-bronze bellows.
Minimum Ambient Temperature: 32° F (0° C)
Maximum Ambient Temperature: 150° F (66° C)
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2152—08
®
CONTROLLERS
Table 1. Models available.
a
Proportioning (Throttling) Range at Midscale
Potentiometer
Metric Units
Part No.
23176CB
23176CF
23176CF
U. S.
Customary
b
Adjustable
Units
No
0.5 psi
No
5 psi
No
12 psi
Yes
1.5 to 12 psi
Yes
5 to 23 psi
Yes
12 to 48 psi
Yes
30 to 110 psi
Yes
1.5 to 12 psi
Yes
13 to 52 psi
Yes
30 to 110 psi
Adjustment Means: Screws on controller case top; knurled
knob for main scale setting on 10 to 300 psi (0.07 to 2.07
MPa) models.
Setpoint: At low pressure end of proportioning (throttling)
range.
Main Scaleplate: Marked in both U.S. customary (oz/sq. in,
psi, or in. Hg) and metric (kPa, MPa, or mm Hg) units.
Proportioning Range Scaleplate (L91B,D only): Gradu-
ated from A to F with a MIN (minimum) value below A.
(See Table 2 for the value of each division.)
Mounting Means: Fitting on bellows has 1/4 - 18 NPT
threads (external on 0 to 16 oz/sq. in., 0 to 4 psi, and 0 to
15 psi models; internal on all other models) for mounting on
a pipe or steam trap (siphon loop).
NOTE: Some models are available with 1/4 - 19 BSP-TR
internal threads; see Table 1.
Also can be surface mounted by screws through two knockout
holes in case back.
2
Maximum Surge
Pressure
Metric Units
psi
3.4 kPa 25
172
0.03 MPa
225
0.08 MPa
350
10 to 83 kPa
25
35 to 160 kPa
225
85 to 330 kPa
350
0.21 to 0.76 MPa 350
10 to 83 kPa
25
0.09 to 0.36 MPa 225
0.21 to 0.76 MPa 350
kPa
1551
2413
172
1551
2413
2413
172
1551
2413

Hide quick links:

Advertisement

loading

This manual is also suitable for:

L91bL91d