Venting Methods - Jenn-Air W10526082A Installation Instructions Manual

30" (76.2 cm) gas downdraft slide-in ranges
Table of Contents

Advertisement

Available languages

Available languages

The length of vent system and number of elbows should be kept
to a minimum to provide efficient performance.
The maximum equivalent length of the vent system is 60 ft
(18.3 m). For altitudes above 4,500 ft (1272 m), reduce
recommended vent run by 20% for best performance.
Cold Weather Installations
An additional backdraft damper should be installed to minimize
backward cold air flow and a thermal break installed to minimize
conduction of outside temperatures as part of the vent system.
The damper should be on the cold air side of the thermal break.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.

Venting Methods

Common venting methods are shown for a downdraft range. The
downdraft range may be vented through the wall or floor.
Wall Venting
A. Wall cap
B. 6" (15.2 cm) round roof venting
Floor Venting
Venting Between Floor Joists
A
B
A. Wall cap
B. 3¼ x 10" (8.3 x 25.4 cm) round roof venting
6
A
B
Side Venting
Venting Behind Cabinet Kick Plate
A
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
Concrete Slab Installations - Exhaust Through Wall
B
A
L
K
J
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. Concrete slab
F. 6" (15.2 cm) round PVC sewer pipe
G. 6" (15.2 cm) round 90° PVC sewer pipe elbow
H. Tightly pack gravel or sand completely around pipe.
I. 30 ft (9.1 m) max.
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. 6" (15.2 cm) round PVC coupling
L. 12" (30.5 cm) minimum
Concrete Slab Installations -
Exhaust Through Window Well
IMPORTANT: Window well installation for electric models only.
B
A
C
K
J
I
A. Wall cap
B. 12" (30.5 cm) minimum
C. Concrete slab
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round PVC sewer pipe
F. 6" (15.2 cm) round 90° PVC sewer pipe elbow
G. Tightly pack gravel or sand completely around pipe.
H. 42 ft (12.8 m) max.
I. 6" (15.2 cm) round PVC coupling
J. 6" (15.2 cm) minimum
K. Window well
D
C
E
F
G
I
H
D
E
F
H
G

Advertisement

Table of Contents
loading

Table of Contents